Constructed teaching example. This walkthrough is fictional and deliberately typical: the machine, addresses, and numbers are invented to demonstrate the method, and no real capture data appears. Real investigations are messier — but the sequence is the same. It follows the 8-step diagnostics methodology step by step.

Step 1 — Define the Symptom Precisely

The maintenance ticket says: “Conveyor 2 network keeps dropping.”

After talking to the operator and reading the PLC fault log, the real symptom statement becomes:

PLC 192.168.10.10 loses the cyclic EtherNet/IP I/O connection to VFD 192.168.10.40 (conveyor 2 drive) one to three times per day-shift. Each dropout lasts 2–5 seconds, the PLC logs connection fault code and auto-reconnects, and the line stops on the drive’s comm-loss trip. Night shift reports it rarely. It started roughly two weeks ago.

Already useful: it’s one device pair, it’s intermittent, it self-recovers, and it correlates with day shift — which is when the cell is busiest and when people are moving around the machine.

Step 2 — Establish the Boundary

The path is: PLC → panel patch cord → managed switch SW-01 port 1 → port 4 → bulkhead → 18 m field cable in cable tray → VFD. The HMI (192.168.10.20, port 2) never logs comm errors — so the switch and the PLC side are probably healthy, and suspicion narrows to the port-4 leg.

Step 3 — Physical Checks First

Visual inspection finds nothing obviously wrong: connectors seated, no crushed cable visible, drive grounded. Worth noting for later: the port-4 field cable shares a tray section with the conveyor 2 motor cable for about 6 m, and a VFD output-cable separation rule exists on the drawings but the tray divider was never installed.

Nothing conclusive — resist the urge to declare victory here. Log it, keep going.

Step 4 — Configuration Checks

Nothing configured wrong, but one timeline fact emerges from the ticket system: conveyor 2’s motor was replaced two-and-a-half weeks ago.

Step 5 — Device and Switch Diagnostics

Switch port counters (see interpreting port counters):

Counter Port 1 (PLC) Port 2 (HMI) Port 4 (VFD)
CRC/FCS errors 0 0 14,712 and climbing
Link up/down events 0 0 0
Output discards 0 0 0

Counters are cleared and re-read an hour later: port 4 accumulates a few hundred more CRC errors — only while the conveyor is running.

This is the pivot point of the investigation: CRC errors are a physical-layer signature, the link never actually drops, and the errors correlate with motor operation.

Step 6 — Capture with a Plan

Hypothesis: noise-induced frame corruption on the port-4 leg occasionally destroys enough consecutive cyclic packets to trip the connection timeout.

Corrupted frames are discarded by the switch port hardware, so the capture plan is to mirror port 4 and watch for gaps, not errors: a ring-buffer capture (5-minute files × 24) runs on a mirror of port 4, and the operator writes down the wall-clock time of each trip. Capture-laptop clock offset vs PLC clock: recorded (+3 s).

At 10:41 the line trips. The file covering 10:40–10:45 shows, using the I/O Graph: a flat ~50 packet/s cyclic band in each direction, then the VFD→PLC direction thins and stops for ~2.1 s while the PLC→VFD direction continues, then a burst of connection re-establishment (Forward Open) and the band resumes. TCP keepalive and explicit traffic from other devices continue normally throughout — the segment itself never died; frames from the drive stopped surviving the trip down that one cable.

Step 7 — Compare Against a Baseline

A capture of the identical mirror during night shift (conveyor idling) shows the same cyclic band with zero gaps over two hours, and port-4 CRC counters stay frozen. The fault signature exists only under motor load.

Step 8 — Prove Root Cause, Not Correlation

Evidence chain assembled so far:

  1. CRC errors accumulate on port 4 only, only under motor load
  2. Capture shows one-directional cyclic loss with the rest of the segment healthy
  3. Timeline matches the motor replacement — after which the (never-divided) tray section carries a new motor cable pressed directly against the Ethernet field cable
  4. Cable certification test on the port-4 field run: fails return-loss margin near the tray section

Fix: re-route the Ethernet cable to the divided side of the tray per the original drawing and replace the marginal run. Verification: CRC counters stay at zero across three full day-shifts, no trips, and a repeat capture shows an unbroken cyclic band. Root cause proven by elimination and reproduction — not just plausibility.

What Made This Work

Investigations that skip these steps still end — usually with a swapped switch, an unexplained recovery, and a fault that returns in a month.

Trust Boundary — Engineering Judgment Required

This site is an independent educational reference for industrial automation standards. It paraphrases and organizes guidance in original language; it is not a substitute for the official published standards, professional engineering judgment, or legal review, and content has not been independently verified against current published editions.