Packet Capture Methods
Where you attach the analyzer decides what you can see. On a switched network, most capture attempts fail before Wireshark even opens — because the packets never reach the capture port.
Overview
Modern Ethernet is switched: frames are forwarded only to the port that needs them. A laptop plugged into a spare switch port sees broadcast traffic, multicast it happens to receive, and its own conversations — and normally nothing else. Traffic between a PLC and a drive on two other ports is invisible to it. Every capture plan starts by answering one question: how do the packets I care about physically reach my capture interface?
There are four answers, each with real trade-offs.
flowchart TD
PLC[PLC] --- SW[Managed Switch]
SW --- VFD[VFD]
SW --- EWS[Engineering Workstation<br/>Method 1: local capture]
SW -. "mirror of PLC port" .-> AN1[Analyzer<br/>Method 2: SPAN]
PLC --- TAP[Inline TAP<br/>Method 3] --- SW2[to switch]
TAP -.-> AN2[Analyzer]
The Four Methods
Method 1 — Capture on the engineering workstation
Run Wireshark on the machine that is itself one end of the conversation. Useful for traffic that originates or terminates there: OPC UA clients, SCADA polling, programming software, device web interfaces, Modbus TCP test clients.
- Sees: everything to and from that workstation.
- Does not see: PLC-to-drive or any other third-party traffic passing elsewhere through the switch. This is the classic false negative — “I captured and the network is fine” when the capture never contained the traffic in question.
- Cost/risk: none; no production change required. That is exactly why it is over-trusted.
Method 2 — Managed-switch port mirroring (SPAN)
Configure the switch to copy traffic from a source port (or VLAN) to a destination port where the analyzer sits. Usually the best general-purpose method on industrial networks.
Configure: source port, destination port, direction (RX, TX, or both — normally both), and optionally a VLAN source.
Risks and limits:
- Oversubscription — mirroring a full-duplex port means up to two ports’ worth of traffic into one destination; mirroring several busy ports or a VLAN can exceed the destination’s capacity.
- Wrong direction selected — an RX-only mirror silently hides half the conversation, which reads as “the device never replied”.
- Mirror drops under load — most switches deprioritize mirrored frames; the capture can be missing exactly the packets from the moment of the fault. A gap in a SPAN capture is weaker evidence than a gap in a TAP capture.
- Production change — changing the configuration of a production switch normally requires authorization. Get it, and record what you changed so it can be reverted.
Method 3 — Network TAP
A TAP (test access point) is installed inline in the link and copies both directions to the analyzer. It is the most faithful method: it observes both directions at full rate, does not depend on switch configuration, and a good TAP does not drop frames.
Risks and limits:
- Insertion requires a link interruption — the cable must be unplugged to install the TAP. On a running machine that is an outage; plan it, or install TAPs permanently at key points during commissioning.
- Link-negotiation influence — copper TAPs sit in the negotiation path and can influence speed/duplex negotiation; verify the link comes back up at the expected rate after insertion.
- Hardware suitability — the TAP must match the link speed and be appropriate for the industrial environment (temperature, mounting, power).
Method 4 — Legacy hub
An old half-duplex hub repeats every frame to every port, so a laptop on a hub sees everything. It is generally a poor method: it forces half-duplex operation, reintroduces collisions, and changes the timing behavior of the network it is supposed to observe. Do not use a hub on real-time or safety-related networks without a controlled test plan — the measurement method itself can create the fault, or a new one.
| Method | Sees third-party traffic | Fidelity under load | Production impact to attach |
|---|---|---|---|
| Workstation capture | No | n/a | None |
| Port mirroring (SPAN) | Yes (mirrored ports) | Mirror may drop frames | Switch config change (authorized) |
| Network TAP | Yes (that link) | Highest | Link interruption to insert |
| Hub | Yes (all ports) | Alters network behavior | High — avoid on live systems |
Where to Capture
- As close to the suspect device as possible. A capture near the device distinguishes “device never sent it” from “network lost it”.
- Both sides of a suspected boundary. If a router, firewall, NAT device, or gateway is in the path, capture on both sides simultaneously — the comparison shows exactly what the boundary device altered, delayed, or dropped.
- Match the capture point to the fault boundary established in the diagnostics methodology: a one-device fault wants the capture at that device’s switch port; a machine-wide fault wants the uplink.
Capture Hygiene
- Ring buffers for intermittent faults. Configure Wireshark/dumpcap to write multiple rotating files and leave it running until the symptom recurs. A fault that happens twice per shift will never be caught by a five-minute capture taken when someone is watching.
- Time synchronization. Sync the capture laptop, PLC clock, and switch logs before capturing (NTP where available; otherwise record the offsets). Root-cause arguments live or die on whether timestamps line up.
- Note exactly when symptoms occur. A capture is only searchable if you know where to look — have the operator or a PLC log mark the wall-clock time of each event.
- Record the capture context: capture point, method, mirror configuration, date, machine state. A .pcapng file without context is nearly worthless six months later.
- Take a baseline while the system is healthy, from the same capture point, and archive it with the project.
Ring-Buffer Captures for Intermittent Faults
Intermittent industrial faults may occur once per shift or once per week — a manual five-minute capture will miss them. A ring buffer captures continuously into a rotating set of files so the fault is always inside the retained window when it finally happens.
Time-based rotation with TShark (Wireshark’s command-line capture tool):
tshark \
-i 1 \
-b duration:300 \
-b files:24 \
-w industrial-network-ring.pcapng
- each file holds five minutes; 24 files retain roughly the last two hours
- older files are overwritten automatically, so disk usage stays bounded
- confirm the correct interface number first (
tshark -Dlists them) - note the wall-clock time whenever the symptom occurs, then pull the file covering that window
Size-based rotation works the same way where traffic volume varies:
tshark \
-i 1 \
-b filesize:100000 \
-b files:20 \
-w capture-ring.pcapng
Verify exact option syntax against the TShark version in use.
Confidentiality
Never share packet captures from an employer’s or customer’s network — not in forum posts, not in vendor support tickets without approval, not in a public “capture library”. Captures expose IP addressing schemes, hostnames, device identities and firmware revisions, and operational data (setpoints, recipes, production timing). Treat a capture file with the same confidentiality as the network documentation itself. If a capture must be shared for support, get authorization and sanitize it first — and be aware that sanitization tools have limits.
Common Faults
| Symptom | Likely causes | First checks |
|---|---|---|
| Capture shows almost nothing but broadcasts | Method 1 on a switched network — the traffic never reaches the laptop | Use SPAN or a TAP; confirm what the capture point can physically see |
| Only one direction of a conversation visible | RX-only or TX-only mirror; capturing on the wrong VLAN | Mirror direction setting; VLAN membership of source and destination |
| Gaps in the capture during the fault window | SPAN oversubscription or mirror deprioritization under load | Compare mirrored volume vs destination port rate; retry with a TAP |
| Link went down when the TAP was inserted | Expected — insertion interrupts the link; negotiation settled differently | Verify speed/duplex after insertion; schedule insertions as planned work |
| Wireshark reports dropped packets | Capture machine too slow, USB NIC limits, disk bottleneck | dumpcap with ring buffer, disable name resolution, faster capture hardware |
| Timestamps don’t match PLC fault log | Clocks not synchronized before capture | Sync via NTP or record offsets; re-capture if correlation is the goal |
| Network misbehaved while a hub was inline | Half-duplex operation and collisions introduced by the hub | Remove the hub; use a TAP; treat any hub findings as suspect |
| Capture works on the bench, not on the machine | Different capture point sees different traffic; machine traffic stays local to its switch | Map the topology; move the capture point inside the fault boundary |
Related Pages
- Network Diagnostics Methodology — the workflow these captures belong to (capture is step 6, not step 1)
- Managed Switches — configuring port mirroring and reading port counters
- Industrial Ethernet Fundamentals — why switched networks forward the way they do
- EtherNet/IP / PROFINET / Modbus TCP — protocol-specific filters once the capture exists
- Modbus RTU over RS-485 — serial buses need different capture hardware entirely
- IEC 62443 — captures are sensitive artifacts under a security program
This site is an independent educational reference for industrial automation standards. It paraphrases and organizes guidance in original language; it is not a substitute for the official published standards, professional engineering judgment, or legal review, and content has not been independently verified against current published editions.