Page review information
Edition covered
Project evidence register — Phase 49a findings, 2026-07-13
Content status
Reviewed
Coverage
Phase 49b method register; chemical and biological authority ceilings set by the Phase 49c evidence closure
Last reviewed
August 2026
Primary reference
The official published standard — required for final decisions

Confirm the governing edition, jurisdiction, and project-specific requirements before applying anything on this page.

Safety boundary: no learned method in this register is assigned direct closed-loop authority (level 5) or a safety function. Every row now carries an evidenced ceiling — as of Phase 49c no row is left at “Planned”. The safety-function path never routes through a learned layer — see the safety boundary.

How to read the register

Use the family sections to scan by problem type. Each family opens with a comparison table; the entries below it put the poor-fit and failure cases beside the claimed value so method selection does not become a capability catalogue.

How to read an entry. Every entry answers the same questions, in the same order: what it computes; a concrete example; where it runs; the simpler method it must beat; when it earns its place; when it does not; how much data it needs; why its authority is capped where it is; the tests it must pass; how it fails; what keeps the plant safe anyway; and how strong the evidence is. If an entry’s “poor fit” line describes your situation, the answer is usually the entry’s own “must beat” method. The example lines are illustrative — a typical use that stays within the method’s stated scope, not a documented deployment or an endorsement of a specific product.

Maturity describes deployment reality: industrially routine (widely deployed practice), piloted (documented industrial pilots), research (literature and lab evidence only). Evidence strength names the best available source class for the row: standards body, peer-reviewed, preprint, mixed, or engineering judgement.

Classical deterministic

Method Max authority Must beat Maturity
PID control ≤ 5 On/off or state feedback control industrially routine
Feedforward control ≤ 5 Feedback-only control industrially routine
Rule engine / sequence logic ≤ 5 Hardwired relay logic or state machine industrially routine
System identification ≤ 2 First-principles modelling or manual step-test fit industrially routine
Statistical process control ≤ 2 Engineering limits and alarm rationalisation industrially routine
First-principles numerical model ≤ 4 Empirical correlation or direct measurement industrially routine
PID control — authority ≤ 5 · industrially routine
Computes
Computes control effort from present, accumulated, and rate error.
Example
Holding a pump discharge pressure at setpoint by trimming the VFD speed each scan.
Placement
device
Must beat
On/off or state feedback control
Use when
A measurable process has adequate dynamics and a stable operating envelope.
Poor fit when
Constraints, long delays, or strong interactions dominate.
Data burden
Step tests or operating history for tuning; no training set.
Authority basis
Mature deterministic baseline; project risk assessment still determines permitted control and safety roles.
Validation
Loop-direction, saturation, mode-transfer, disturbance, and fail-state tests.
Failure modes
Windup, noise amplification, oscillation, and hidden mode errors.
Independent protection
Trips and safety functions remain independent of the basic control loop.
Evidence / maturity
mixed / industrially routine
Sources
Control Theory Field Guide
Feedforward control — authority ≤ 5 · industrially routine
Computes
Offsets a measured disturbance before feedback error develops.
Example
Adding heater output the moment a cold-feed flow rise is measured, before the outlet temperature falls.
Placement
device
Must beat
Feedback-only control
Use when
The disturbance is measurable and its process effect is sufficiently known.
Poor fit when
Disturbance measurement or model sign and gain are unreliable.
Data burden
A validated disturbance-to-output model; no ML training set.
Authority basis
Deterministic control whose deployment authority is established by the project control and risk design.
Validation
Sign, scaling, timing, saturation, and feedback-recovery tests.
Failure modes
Wrong-sign action, timing mismatch, and excessive compensation.
Independent protection
Independent limits and trips constrain commanded output.
Evidence / maturity
mixed / industrially routine
Sources
Control Theory Field Guide
Rule engine / sequence logic — authority ≤ 5 · industrially routine
Computes
Maps explicit conditions and states to deterministic actions.
Example
Sequencing a filling station: clamp, fill to weight, cap, release, in a reviewed, fully testable state machine.
Placement
device
Must beat
Hardwired relay logic or state machine
Use when
Required behaviour can be stated, reviewed, and exhaustively tested.
Poor fit when
The state space cannot be bounded or requirements are ambiguous.
Data burden
Requirements and test cases; no training data.
Authority basis
Deterministic implementation; authority follows verified requirements, not this catalogue.
Validation
State, transition, timeout, restart, and abnormal-path coverage.
Failure modes
Missing transition, conflicting rule, stale latch, and unsafe restart.
Independent protection
Safety logic uses its required independent and certified architecture.
Evidence / maturity
mixed / industrially routine
Sources
Control Theory Field Guide
System identification — authority ≤ 2 · industrially routine
Computes
Fits a dynamic input-output model from designed or historical excitation.
Example
Fitting a heat-exchanger step-response model offline from a designed bump test, for later controller tuning.
Placement
engineering workstation
Must beat
First-principles modelling or manual step-test fit
Use when
A model is needed and safe excitation covers the intended envelope.
Poor fit when
Inputs lack excitation, data leak future information, or the plant changes materially.
Data burden
Time-aligned, sufficiently excited input-output data and validation runs.
Authority basis
Model construction is offline; any downstream controller requires a separate authority case.
Validation
Residual independence, held-out transients, stability, and physical-sanity checks.
Failure modes
Confounding, non-identifiability, extrapolation, and unstable fitted dynamics.
Independent protection
Identification experiments obey independent operating constraints.
Evidence / maturity
mixed / industrially routine
Sources
Control Theory Field Guide
Statistical process control — authority ≤ 2 · industrially routine
Computes
Detects statistically unusual process shifts against an established baseline.
Example
Detecting a slow drift in fill weight against an established stable-baseline control chart.
Placement
historian/analytics
Must beat
Engineering limits and alarm rationalisation
Use when
The process has a stable baseline and special-cause detection is useful.
Poor fit when
Operating modes are mixed or distribution assumptions are ignored.
Data burden
Mode-labelled baseline data with known quality.
Authority basis
Advisory quality or maintenance signal; not a safety trip.
Validation
False-alarm rate, mode separation, sensitivity, and recalibration review.
Failure modes
Alarm flooding, missed drift, autocorrelation bias, and baseline contamination.
Independent protection
Engineered alarms, trips, and product disposition remain independent.
Evidence / maturity
mixed / industrially routine
Sources
NIST AI Risk Management Framework 1.0 (NIST AI 100-1)
First-principles numerical model — authority ≤ 4 · industrially routine
Computes
Solves governing physical equations for prediction or estimation.
Example
Solving the governing heat-transfer equations to predict jacket temperature for a new recipe.
Placement
edge
Must beat
Empirical correlation or direct measurement
Use when
Governing physics and parameters are known well enough for the decision.
Poor fit when
Unknown closure relations dominate or solve time exceeds freshness needs.
Data burden
Geometry, properties, boundary conditions, and calibration measurements.
Authority basis
Deterministic model; bounded authority still requires verification, timing, and fallback.
Validation
Mesh/time convergence, conservation, parameter sensitivity, and plant comparison.
Failure modes
Wrong boundary condition, numerical instability, parameter error, and stale solve.
Independent protection
Safety limits rely on independent validated channels.
Evidence / maturity
mixed / industrially routine
Sources
Control Theory Field Guide

Estimation

Method Max authority Must beat Maturity
Kalman filter ≤ 4 Direct measurement or fixed low-pass filtering industrially routine
EKF / UKF nonlinear estimator ≤ 3 Observer, direct sensor, or linear Kalman filter industrially routine
PCA / PLS latent-variable model ≤ 2 Selected sensors, mass balance, or linear regression industrially routine
Gradient-boosted trees ≤ 2 Rules, linear model, or physics-based correlation industrially routine
Gaussian-process regression ≤ 2 Physical correlation, interpolation, or linear regression piloted
Learned soft sensor ≤ 2 Physical sensor, material balance, or PLS model piloted
Online adaptive learning ≤ 0 Scheduled fixed models with reviewed offline updates research
Kalman filter — authority ≤ 4 · industrially routine
Computes
Fuses a linear dynamic model and noisy measurements into a state estimate.
Example
Estimating true tank level from a noisy level transmitter fused with the inlet/outlet flow balance.
Placement
device
Must beat
Direct measurement or fixed low-pass filtering
Use when
The linear model and noise assumptions are adequate and hidden states matter.
Poor fit when
Dynamics are strongly nonlinear or noise assumptions are badly violated.
Data burden
Model, covariance estimates, and representative disturbances.
Authority basis
Deterministic estimator may support bounded control after project-specific observability and fault analysis.
Validation
Innovation residuals, observability, sensor-loss, initialization, and numerical tests.
Failure modes
Divergence, biased estimate, covariance mismatch, and silent sensor fault absorption.
Independent protection
Safety decisions do not depend solely on the estimate.
Evidence / maturity
mixed / industrially routine
Sources
Control Theory Field Guide
EKF / UKF nonlinear estimator — authority ≤ 3 · industrially routine
Computes
Estimates nonlinear process states using local linearization or sigma points.
Example
Estimating unmeasured reactor concentration from temperature and flow through a validated nonlinear model.
Placement
edge
Must beat
Observer, direct sensor, or linear Kalman filter
Use when
A nonlinear model is credible and missing states materially improve operation.
Poor fit when
The model is weak, states are unobservable, or compute timing is not bounded.
Data burden
Validated model, uncertainty assumptions, and transient cases.
Authority basis
Conservative ceiling pending application-specific estimator fault containment.
Validation
Monte Carlo transients, residual checks, sensor faults, and timing tests.
Failure modes
Divergence, local-linearization error, false confidence, and late output.
Independent protection
Independent sensors and protection remain authoritative.
Evidence / maturity
engineering judgement / industrially routine
Sources
Control Theory Field Guide; NIST AI Risk Management Framework 1.0 (NIST AI 100-1)
PCA / PLS latent-variable model — authority ≤ 2 · industrially routine
Computes
Compresses correlated variables or predicts a response from latent factors.
Example
Compressing dozens of correlated batch sensors into a few latent trends to spot an off-normal batch.
Placement
historian/analytics
Must beat
Selected sensors, mass balance, or linear regression
Use when
Variables are correlated and a validated low-dimensional structure is stable.
Poor fit when
Modes shift, nonlinearities dominate, or causal interpretation is required.
Data burden
Representative, scaled, mode-labelled data with reference responses for PLS.
Authority basis
Advisory ceiling unless an independent application case proves bounded use.
Validation
Held-out batches, leverage and residual limits, drift, and missing-data tests.
Failure modes
Spurious correlation, latent-space extrapolation, leakage, and scaling errors.
Independent protection
Direct measurements and protection remain authoritative.
Evidence / maturity
engineering judgement / industrially routine
Sources
NIST AI Risk Management Framework 1.0 (NIST AI 100-1)
Gradient-boosted trees — authority ≤ 2 · industrially routine
Computes
Predicts a class or value using an ensemble of sequential decision trees.
Example
Predicting product quality grade from tabular process settings, held out by asset, as a lab-check advisory.
Placement
edge
Must beat
Rules, linear model, or physics-based correlation
Use when
Tabular nonlinear interactions are stable and beat simpler baselines on held-out assets.
Poor fit when
Extrapolation or causal physical behaviour is required.
Data burden
Representative labelled tabular data with leakage-safe splits.
Authority basis
Advisory ceiling; explainability does not establish safe authority.
Validation
Asset/time holdout, calibration, shift, missing-input, fairness, and drift tests.
Failure modes
Leakage, threshold discontinuity, missing-value shortcut, and extrapolation error.
Independent protection
Independent sensors and limits remain authoritative.
Evidence / maturity
engineering judgement / industrially routine
Sources
NIST AI Risk Management Framework 1.0 (NIST AI 100-1)
Gaussian-process regression — authority ≤ 2 · piloted
Computes
Predicts a quantity with a kernel-based uncertainty estimate.
Example
Estimating a hard-to-measure yield with calibrated uncertainty from a small, modest-dimension dataset.
Placement
edge
Must beat
Physical correlation, interpolation, or linear regression
Use when
Data are limited, dimensionality is modest, and calibrated uncertainty is valuable.
Poor fit when
Datasets are large, inputs are high-dimensional, or kernel assumptions fail.
Data burden
Representative input-output samples and justified kernel design.
Authority basis
Uncertainty is model-dependent; use remains advisory without a separate bounded case.
Validation
Coverage calibration, out-of-domain challenge, sensitivity, and compute tests.
Failure modes
False uncertainty, kernel misspecification, scaling cost, and extrapolation.
Independent protection
Protection does not rely on posterior confidence.
Evidence / maturity
engineering judgement / piloted
Sources
NIST AI Risk Management Framework 1.0 (NIST AI 100-1)
Learned soft sensor — authority ≤ 2 · piloted
Computes
Infers a difficult-to-measure process variable from easier measurements.
Example
Inferring a stream composition between lab assays from temperature, pressure, and flow measurements.
Placement
edge
Must beat
Physical sensor, material balance, or PLS model
Use when
Reference measurements cover the operating envelope and maintenance value is clear.
Poor fit when
The target cannot be periodically measured or input sensors share common failures.
Data burden
Time-aligned reference assays or sensors across modes, lots, and drift.
Authority basis
Advisory ceiling because inferred measurement is vulnerable to drift and shared-cause error.
Validation
Time/lot holdout, uncertainty, sensor-fault, drift, and reference-reconciliation tests.
Failure modes
Target drift, lag mismatch, shared sensor bias, and confident extrapolation.
Independent protection
Independent direct measurement or conservative limits protect critical decisions.
Evidence / maturity
engineering judgement / piloted
Sources
NIST AI Risk Management Framework 1.0 (NIST AI 100-1)
Online adaptive learning — authority ≤ 0 · research
Computes
Updates model parameters from live operating data.
Example
Continuously retuning a model from live data — kept offline here until update bounds and rollback are fully controlled.
Placement
edge
Must beat
Scheduled fixed models with reviewed offline updates
Use when
Update bounds, acceptance tests, rollback, and drift causes are fully controlled.
Poor fit when
The context is certified, safety-related, adversarial, or labels arrive late.
Data burden
Live data, trustworthy feedback, bounded update rules, and retained baseline data.
Authority basis
Phase 49a recommends offline-only treatment in certified or safety-relevant contexts.
Validation
Shadow mode, update bounds, poisoning, rollback, reproducibility, and change-control tests.
Failure modes
Catastrophic forgetting, poisoning, feedback loop, silent drift, and unreproducible state.
Independent protection
Live learning is isolated from safety and direct control paths.
Evidence / maturity
standards body / research
Sources
ISO/IEC TR 5469:2024 — Functional safety and AI systems (Technical Report: guidance, not certifiable requirements); Regulation (EU) 2023/1230 on machinery; Regulation (EU) 2024/1689 — Artificial Intelligence Act

Optimisation

Method Max authority Must beat Maturity
Moving-horizon estimation ≤ 3 Kalman filter or deterministic observer industrially routine
Model predictive control ≤ 4 PID, feedforward, selectors, and override control industrially routine
Robust MPC / safety filter ≤ 3 Hard selectors, clamps, permissives, and override control piloted
Reinforcement-learning policy ≤ 3 MPC, dynamic programming, rules, or operator procedure research
Moving-horizon estimation — authority ≤ 3 · industrially routine
Computes
Solves a constrained recent-history optimisation to estimate states and disturbances.
Example
Reconciling recent flow, level, and composition history against constraints to estimate an unmeasured disturbance.
Placement
edge
Must beat
Kalman filter or deterministic observer
Use when
Constraints and nonlinear dynamics justify the compute and engineering cost.
Poor fit when
A simple observer is adequate or solve time cannot be guaranteed.
Data burden
Process model, constraints, noise assumptions, and transient history.
Authority basis
Bounded use requires deterministic timeout and fallback behaviour.
Validation
Feasibility, convergence, worst-case timing, fault injection, and fallback tests.
Failure modes
Infeasible solve, local optimum, stale estimate, and model mismatch.
Independent protection
Protection must tolerate estimator loss or error.
Evidence / maturity
engineering judgement / industrially routine
Sources
Control Theory Field Guide
Model predictive control — authority ≤ 4 · industrially routine
Computes
Optimises future manipulated variables against a model and constraints.
Example
Holding a distillation column inside purity and flooding limits while minimising reboiler energy.
Placement
supervisory
Must beat
PID, feedforward, selectors, and override control
Use when
Interactions and constraints produce measurable value beyond simpler loops.
Poor fit when
Models, maintenance capacity, or solve-time guarantees are inadequate.
Data burden
Validated dynamic model, constraints, estimator, and disturbance scenarios.
Authority basis
Deterministic bounded supervisory control with independent basic and protective layers.
Validation
Constraint, infeasibility, model mismatch, timing, bumpless fallback, and cyber tests.
Failure modes
Bad model, infeasible optimisation, stale state, and economically unsafe objective.
Independent protection
SIS, trips, hard limits, and basic regulatory control remain independent.
Evidence / maturity
mixed / industrially routine
Sources
Control Theory Field Guide; NIST SP 800-82 Rev. 3: Guide to Operational Technology Security
Robust MPC / safety filter — authority ≤ 3 · piloted
Computes
Projects a proposed command into a modelled feasible set under uncertainty.
Example
Projecting an operator's proposed setpoint change into a modelled feasible set before it is applied.
Placement
supervisory
Must beat
Hard selectors, clamps, permissives, and override control
Use when
Uncertainty bounds are credible and constraints are too coupled for simple clamps.
Poor fit when
The safe set is incomplete or worst-case solve time is unbounded.
Data burden
Verified model, uncertainty set, constraints, and adversarial scenarios.
Authority basis
Phase 49a supports only operator-approved use absent an independently verified veto architecture.
Validation
Reachability, infeasibility, timing, uncertainty-bound, and fallback evidence.
Failure modes
False feasible set, numerical failure, hidden constraint, and unsafe fallback.
Independent protection
Certified protection and hard interlocks remain outside the filter.
Evidence / maturity
engineering judgement / piloted
Sources
ISO/IEC TR 5469:2024 — Functional safety and AI systems (Technical Report: guidance, not certifiable requirements); NIST AI Risk Management Framework 1.0 (NIST AI 100-1)
Reinforcement-learning policy — authority ≤ 3 · research
Computes
Selects actions to maximise a learned or simulated cumulative reward.
Example
Learning a start-up sequence in a high-fidelity simulator, run only behind an independent action envelope.
Placement
supervisory
Must beat
MPC, dynamic programming, rules, or operator procedure
Use when
A high-fidelity environment and independent action envelope show value over deterministic control.
Poor fit when
Unsafe exploration, reward misspecification, or unmodelled rare events cannot be ruled out.
Data burden
Validated simulator or extensive trajectories including disturbances and boundary cases.
Authority basis
Default operator-approved ceiling; level 4 needs an independently verified veto architecture.
Validation
Adversarial scenarios, reward audit, policy stability, shift, constraint, and rollback tests.
Failure modes
Reward hacking, unsafe exploration, simulator gap, brittle policy, and action chattering.
Independent protection
A non-learned envelope vetoes every unsafe or out-of-scope action.
Evidence / maturity
engineering judgement / research
Sources
ISO/IEC TR 5469:2024 — Functional safety and AI systems (Technical Report: guidance, not certifiable requirements); NIST AI Risk Management Framework 1.0 (NIST AI 100-1)

Perception

Method Max authority Must beat Maturity
1D convolutional neural network ≤ 2 Spectral features plus thresholds or a simpler classifier piloted
2D convolutional neural network ≤ 2 Machine vision rules, gauges, or human inspection industrially routine
Temporal transformer ≤ 2 State machine, AR model, engineered windows, or smaller recurrent model piloted
Autoencoder anomaly detection ≤ 2 Limits, residuals, SPC, or one-class statistical model piloted

Split your data the way the plant is split. Random train/test splits overstate perception performance. Leakage in some form — label, future, or normal-data contamination — appears in this family’s failure modes, and each row’s validation names the matching leakage-aware split: asset-held-out, lot-held-out, or a temporal split with a leakage audit.

1D convolutional neural network — authority ≤ 2 · piloted
Computes
Classifies or embeds local patterns in waveform or time-series windows.
Example
Flagging likely bearing wear from accelerometer windows on a pump train, for inspection at the next stop.
Placement
edge
Must beat
Spectral features plus thresholds or a simpler classifier
Use when
Raw local patterns add repeatable value across representative machines and loads.
Poor fit when
Fault labels are sparse, acquisition changes, or a few engineered features suffice.
Data burden
Labelled waveforms spanning assets, loads, sensors, and acquisition conditions.
Authority basis
Advisory diagnostic ceiling; Phase 49a found no basis for learned safety authority.
Validation
Asset-held-out tests, shift tests, calibration, latency, drift, and abstention.
Failure modes
Domain shift, shortcut learning, label leakage, overconfidence, and aliasing.
Independent protection
Protection never depends on the diagnosis or confidence score.
Evidence / maturity
mixed / piloted
Sources
NIST AI Risk Management Framework 1.0 (NIST AI 100-1); ISO/IEC TR 5469:2024 — Functional safety and AI systems (Technical Report: guidance, not certifiable requirements)
2D convolutional neural network — authority ≤ 2 · industrially routine
Computes
Detects or classifies spatial patterns in images or transformed signals.
Example
Classifying surface-finish defects on parts from line-scan images where rule-based vision falls short.
Placement
edge
Must beat
Machine vision rules, gauges, or human inspection
Use when
Appearance variation is representatively sampled and rule-based vision is inadequate.
Poor fit when
Defects are rare, lighting is uncontrolled, or traceable metrology is required.
Data burden
Labelled images across lots, optics, lighting, defects, and acceptable variation.
Authority basis
Advisory or quality-classification ceiling, not a safety function.
Validation
Lot-held-out tests, rare-defect recall, calibration, shift, and camera-fault tests.
Failure modes
Lighting shortcut, missed novel defect, confident misclassification, and camera drift.
Independent protection
Safety sensing and protective stops remain independent.
Evidence / maturity
mixed / industrially routine
Sources
NIST AI Risk Management Framework 1.0 (NIST AI 100-1); ISO/IEC TR 5469:2024 — Functional safety and AI systems (Technical Report: guidance, not certifiable requirements)
Temporal transformer — authority ≤ 2 · piloted
Computes
Models long-range dependencies in multivariate event or sensor sequences.
Example
Predicting a developing process upset from long multivariate sensor and event history, as an operator advisory.
Placement
historian/analytics
Must beat
State machine, AR model, engineered windows, or smaller recurrent model
Use when
Long context adds validated value that simpler temporal models do not deliver.
Poor fit when
Data volume, timing, or interpretability cannot support the complexity.
Data burden
Large time-aligned sequences with mode, maintenance, and outcome labels.
Authority basis
Conservative advisory ceiling under the NIST AI risk-management lifecycle.
Validation
Temporal split, leakage audit, calibration, shift, ablation, and latency tests.
Failure modes
Future leakage, mode confounding, attention instability, drift, and high compute.
Independent protection
Independent alarms and trips remain effective during wrong or missing predictions.
Evidence / maturity
engineering judgement / piloted
Sources
NIST AI Risk Management Framework 1.0 (NIST AI 100-1); ISO/IEC TR 5469:2024 — Functional safety and AI systems (Technical Report: guidance, not certifiable requirements)
Autoencoder anomaly detection — authority ≤ 2 · piloted
Computes
Flags samples that reconstruct poorly relative to learned normal data.
Example
Flagging a compressor operating pattern that reconstructs poorly against learned normal running, for investigation.
Placement
edge
Must beat
Limits, residuals, SPC, or one-class statistical model
Use when
Normal operation is well sampled and unknown deviations merit investigation.
Poor fit when
Normal modes evolve rapidly or anomaly scores cannot be tied to action.
Data burden
Clean, representative normal data plus known faults for challenge testing.
Authority basis
Anomaly score is advisory because unknown does not establish hazardous or faulty state.
Validation
Known-fault challenge, false-alarm, mode, shift, calibration, and abstention tests.
Failure modes
Normal-data contamination, mode alarm, missed familiar anomaly, and opaque score.
Independent protection
Engineered protections cannot be replaced by anomaly detection.
Evidence / maturity
engineering judgement / piloted
Sources
NIST AI Risk Management Framework 1.0 (NIST AI 100-1)

Physics informed

Method Max authority Must beat Maturity
PINN forward model ≤ 1 Finite-volume, finite-element, or ordinary differential equation solver research
PINN inverse parameter model ≤ 1 Constrained optimisation around a numerical solver research
Hybrid physics plus learned residual ≤ 2 Recalibrated physics model or explicit empirical correction piloted
Learned chemical closure model ≤ 2 Mechanistic closure, tabulation, or conservative correlation research
PINN forward model — authority ≤ 1 · research
Computes
Fits a neural approximation while penalising governing-equation residuals.
Example
Approximating a repeated diffusion solve as a research alternative to a numerical solver, benchmarked against it.
Placement
engineering workstation
Must beat
Finite-volume, finite-element, or ordinary differential equation solver
Use when
A differentiable physics prior and repeated-query need survive comparison with numerical solvers.
Poor fit when
Classical numerics are accurate and affordable or stiff/multiscale optimisation fails.
Data burden
Equations, boundary conditions, collocation points, and validation measurements.
Authority basis
Phase 49a failure evidence supports read-only use; classical numerics remain the baseline.
Validation
Conservation, boundary residual, mesh-independent reference, extrapolation, and repeatability tests.
Failure modes
Optimisation failure, spectral bias, nonunique fit, and deceptively low aggregate loss.
Independent protection
No safety or loop-closing decision relies on the PINN output.
Evidence / maturity
peer-reviewed / research
Sources
Physics-informed neural networks; Characterizing possible failure modes in physics-informed neural networks; Predictive Limitations of Physics-Informed Neural Networks in Vortex Shedding (Chuang & Barba)
PINN inverse parameter model — authority ≤ 1 · research
Computes
Infers model parameters or hidden fields while enforcing equation residuals.
Example
Recovering an unknown diffusivity field from sensor data while enforcing the governing-equation residual, in research.
Placement
engineering workstation
Must beat
Constrained optimisation around a numerical solver
Use when
The inverse problem is identifiable and PINN performance beats the numerical baseline.
Poor fit when
Parameters are non-identifiable or boundary data are incomplete.
Data burden
Governing equations, informative measurements, uncertainty, and synthetic recovery cases.
Authority basis
Read-only ceiling due inverse non-uniqueness and documented PINN training failures.
Validation
Parameter-recovery studies, identifiability, noise, multiple starts, and solver comparison.
Failure modes
Plausible wrong parameter, compensating errors, local minimum, and false confidence.
Independent protection
Inferred parameters cannot directly change protective settings.
Evidence / maturity
peer-reviewed / research
Sources
Physics-informed neural networks; Characterizing possible failure modes in physics-informed neural networks; Predictive Limitations of Physics-Informed Neural Networks in Vortex Shedding (Chuang & Barba)
Hybrid physics plus learned residual — authority ≤ 2 · piloted
Computes
Adds a learned correction to a first-principles prediction.
Example
Adding a small learned correction to a first-principles temperature model where a stable residual bias remains.
Placement
edge
Must beat
Recalibrated physics model or explicit empirical correction
Use when
Residual structure is stable and improves held-out performance without violating constraints.
Poor fit when
The base model is structurally wrong or residual data lack envelope coverage.
Data burden
Validated base model and representative residuals across regimes.
Authority basis
Advisory ceiling; the learned closure can invalidate physical guarantees.
Validation
Ablation, conservation, regime holdout, uncertainty, drift, and base-model fallback.
Failure modes
Physics cancellation, extrapolated correction, regime shift, and hidden bias.
Independent protection
Independent limits use the uncorrected conservative model or direct measurements.
Evidence / maturity
mixed / piloted
Sources
NIST AI Risk Management Framework 1.0 (NIST AI 100-1); Characterizing possible failure modes in physics-informed neural networks
Learned chemical closure model — authority ≤ 2 · research
Computes
Approximates an unresolved reaction, property, or transport closure inside a physical model.
Example
Approximating an unresolved reaction closure inside a physical model, bounded and validated across every intended regime.
Placement
edge
Must beat
Mechanistic closure, tabulation, or conservative correlation
Use when
The learned closure is bounded, faster, and validated across every intended regime.
Poor fit when
Rare regimes, conservation, positivity, or extrapolation cannot be controlled.
Data burden
High-quality simulation or experiment data spanning regime and uncertainty.
Authority basis
Phase 49c adversarial coverage supports a bounded advisory ceiling for a learned closure; no fitted closure receives hard-constraint or safety-function status.
Validation
Conservation, positivity, regime holdout, uncertainty, drift, and deterministic fallback.
Failure modes
Nonphysical closure, unstable coupling, distribution shift, and hidden compensation.
Independent protection
Independent protection assumes the learned closure can be completely wrong.
Evidence / maturity
preprint / research
Sources
Characterizing possible failure modes in physics-informed neural networks; Phase 49a adversarial evidence findings (internal evidence record; not published); Phase 49c chemical/biological evidence-closure and adversarial findings (internal evidence record; not published)

Language/agentic

Method Max authority Must beat Maturity
LLM engineering copilot ≤ 2 Templates, search, rules, and human engineering review piloted
LLM PLC code drafting ≤ 0 Reviewed templates, libraries, and manual implementation research
Agentic engineering workflow ≤ 0 Scripted workflow with explicit approvals and checks research
LLM engineering copilot — authority ≤ 2 · piloted
Computes
Drafts explanations, analyses, or engineering artefacts from supplied context.
Example
Drafting a functional-description document from supplied P&ID notes for an engineer to review and correct.
Placement
engineering workstation
Must beat
Templates, search, rules, and human engineering review
Use when
Drafting speed helps and every material claim and output can be reviewed.
Poor fit when
Source provenance is absent or the output can directly alter a plant.
Data burden
Approved context, retrieval boundary, prompts, and representative evaluation tasks.
Authority basis
Advisory ceiling; fluent text is not verified engineering evidence.
Validation
Grounding, citation, prompt-injection, confidentiality, repeatability, and expert-review tests.
Failure modes
Hallucination, source confusion, prompt injection, sensitive-data disclosure, and automation bias.
Independent protection
No generated output bypasses engineering review or safety lifecycle controls.
Evidence / maturity
mixed / piloted
Sources
NIST AI Risk Management Framework 1.0 (NIST AI 100-1); NIST AI RMF: Generative AI Profile (NIST AI 600-1, 2024-07-26) — companion to AI RMF 1.0; NIST SP 800-82 Rev. 3: Guide to Operational Technology Security
LLM PLC code drafting — authority ≤ 0 · research
Computes
Produces candidate PLC code or tests from a natural-language requirement.
Example
Drafting a first-pass interlock routine offline that an engineer rewrites and formally checks before any controller sees it.
Placement
engineering workstation
Must beat
Reviewed templates, libraries, and manual implementation
Use when
Generated code remains a draft and formal/static/dynamic checks are effective.
Poor fit when
Requirements are ambiguous or code could reach production without independent verification.
Data burden
Approved examples, language grammar, requirements, and adversarial test tasks.
Authority basis
Offline drafting only; the cited PLC work is a peer-reviewed proof of concept (ICSE 2024 SEIP) and does not establish deployment safety.
Validation
Compile, static analysis, simulation, traceability, mutation, security, and human review.
Failure modes
Invented API, unsafe state path, incomplete requirement, plausible wrong code, and hidden prompt dependency.
Independent protection
Safety application code follows its required lifecycle and independent verification.
Evidence / maturity
peer-reviewed / research
Sources
LLM4PLC: Harnessing Large Language Models for Verifiable Programming of PLCs (Fakih et al.); ISO/IEC TR 5469:2024 — Functional safety and AI systems (Technical Report: guidance, not certifiable requirements)
Agentic engineering workflow — authority ≤ 0 · research
Computes
Plans and invokes tools across a multi-step engineering task.
Example
Planning and running a multi-step documentation task with narrow, reversible tool permissions and gated steps.
Placement
engineering workstation
Must beat
Scripted workflow with explicit approvals and checks
Use when
Tool permissions are narrow, actions are reversible, and each consequential step is gated.
Poor fit when
The agent can change live controls, safety settings, credentials, or unreviewed records.
Data burden
Tool schemas, policy tests, representative tasks, and attack scenarios.
Authority basis
Offline engineering use only; no evidence supports autonomous plant authority.
Validation
Permission, injection, tool-error, rollback, audit-log, and human-approval tests.
Failure modes
Goal drift, unsafe tool choice, injection, cascading error, and false completion claim.
Independent protection
Agent credentials and network paths cannot reach safety or production control authority.
Evidence / maturity
standards body / research
Sources
NIST AI Risk Management Framework 1.0 (NIST AI 100-1); NIST SP 800-82 Rev. 3: Guide to Operational Technology Security

Interface

Method Max authority Must beat Maturity
Edge inference deployment ≤ 2 Stream raw data to a central analytic service industrially routine
OPC UA result publication ≤ 2 Vendor-neutral tags plus documented alarm/event mapping industrially routine
MQTT Sparkplug result publication ≤ 2 OPC UA or a documented application-specific message contract industrially routine
Historian feature pipeline ≤ 2 Direct trend review or explicitly computed reports industrially routine
Digital-twin state synchronisation ≤ 2 SCADA mimic, simulator snapshot, or engineering calculation piloted
Edge inference deployment — authority ≤ 2 · industrially routine
Computes
Runs a validated model near high-rate sensors and publishes a lower-rate result.
Example
Running a validated vibration model on a gateway beside the sensor and publishing only the health verdict upstream.
Placement
edge
Must beat
Stream raw data to a central analytic service
Use when
Bandwidth, latency, privacy, or acquisition rate makes local processing necessary.
Poor fit when
Edge lifecycle, timing, security, and model update controls cannot be maintained.
Data burden
Representative signals plus hardware timing, load, and failure tests.
Authority basis
NIST OT guidance supports local/segmented placement; it does not grant model authority.
Validation
Worst-case latency, resource exhaustion, reboot, version, integrity, and stale-output tests.
Failure modes
Late result, resource starvation, silent model mismatch, and disconnected drift.
Independent protection
Edge failure leaves the plant in a protected, diagnosable state.
Evidence / maturity
standards body / industrially routine
Sources
NIST SP 800-82 Rev. 3: Guide to Operational Technology Security; NIST AI Risk Management Framework 1.0 (NIST AI 100-1)
OPC UA result publication — authority ≤ 2 · industrially routine
Computes
Publishes model result, confidence, version, quality, and freshness as custom structured data.
Example
Publishing a diagnosis with its confidence, model version, quality, and freshness as a structured OPC UA object.
Placement
supervisory
Must beat
Vendor-neutral tags plus documented alarm/event mapping
Use when
Consumers need discoverable semantics, security roles, and quality metadata.
Poor fit when
A polling path is incorrectly expected to reconstruct high-rate source waveforms.
Data burden
Information model, units, timestamps, quality, version, and stale-state contract.
Authority basis
OPC UA transports application-defined results; it has no standard AI-result meaning or authority grant.
Validation
Schema, timestamp, quality, stale, role, reconnect, and consumer-compatibility tests.
Failure modes
Stale good-looking value, semantic mismatch, timestamp loss, and unauthorized write.
Independent protection
Publication failure or corruption cannot defeat independent protection.
Evidence / maturity
standards body / industrially routine
Sources
OPC UA Part 1: Overview and Concepts; OPC UA Part 9: Alarms and Conditions; OPC UA Part 18: Role-Based Security
MQTT Sparkplug result publication — authority ≤ 2 · industrially routine
Computes
Publishes state-aware metrics for model results over MQTT infrastructure.
Example
Publishing model results as state-aware Sparkplug metrics over MQTT for store-and-forward integration.
Placement
supervisory
Must beat
OPC UA or a documented application-specific message contract
Use when
Store-and-forward or brokered integration benefits from Sparkplug state semantics.
Poor fit when
Teams assume Sparkplug standardises AI field meanings or ignore broker/security design.
Data burden
Metric contract including units, timestamp, model version, quality, confidence, and freshness.
Authority basis
Sparkplug defines transport/state behaviour, not standard AI-result semantics or control authority.
Validation
Birth/death, stale, reconnect, duplicate, ordering, authorization, and schema tests.
Failure modes
Retained stale result, semantic collision, broker outage, replay, and metric drift.
Independent protection
Brokered results do not implement safety functions.
Evidence / maturity
standards body / industrially routine
Sources
Sparkplug Specification 3.0; NIST SP 800-82 Rev. 3: Guide to Operational Technology Security
Historian feature pipeline — authority ≤ 2 · industrially routine
Computes
Builds time-aligned, versioned analytic features from retained OT data.
Example
Building versioned, time-aligned features from historian data so an analysis can be reproduced months later.
Placement
historian/analytics
Must beat
Direct trend review or explicitly computed reports
Use when
Repeatable analytics require traceable transforms across long history.
Poor fit when
Sampling, timestamps, modes, and data quality cannot support the target claim.
Data burden
Governed tags, clocks, units, quality flags, modes, lineage, and retention.
Authority basis
Read-only/advisory analytics placement is consistent with segmented OT architecture.
Validation
Time alignment, leakage, unit, replay, lineage, access, and backfill tests.
Failure modes
Future leakage, resampling artefact, unit drift, bad-quality inclusion, and lineage loss.
Independent protection
Historian analytics remain outside safety and real-time control paths.
Evidence / maturity
standards body / industrially routine
Sources
NIST SP 800-82 Rev. 3: Guide to Operational Technology Security; NIST AI Risk Management Framework 1.0 (NIST AI 100-1)
Digital-twin state synchronisation — authority ≤ 2 · piloted
Computes
Aligns model state, plant observations, version, and freshness for comparison or forecasting.
Example
Keeping a simulation aligned with plant observations, with version and freshness, to forecast a defined scenario.
Placement
supervisory
Must beat
SCADA mimic, simulator snapshot, or engineering calculation
Use when
A defined use case needs stateful prediction and every variable has a semantic contract.
Poor fit when
The twin has no owner, calibration path, or stale-state behaviour.
Data burden
Asset identity, topology, state mapping, time sync, parameters, events, and version lineage.
Authority basis
Advisory ceiling until each composing model has a stronger verified authority case; ISO 23247 frames the twin but confers no safety authority.
Validation
State reconciliation, version mismatch, stale data, topology change, and fallback tests.
Failure modes
Twin drift, identity mismatch, stale state, wrong topology, and false fidelity.
Independent protection
The twin cannot override independent interlocks or protection.
Evidence / maturity
engineering judgement / piloted
Sources
NIST AI Risk Management Framework 1.0 (NIST AI 100-1); NIST SP 800-82 Rev. 3: Guide to Operational Technology Security; ISO 23247 — Digital Twin Framework for Manufacturing (Parts 1-4:2021; Part 5:2026)

Chemical kinetic

Method Max authority Must beat Maturity
Mass and energy balance ≤ 3 Direct inventory and flow reconciliation industrially routine
Arrhenius reaction-kinetics model ≤ 2 Validated empirical rate table or conservative design case industrially routine
Equilibrium thermodynamic model ≤ 2 Validated property package, laboratory data, or conservative bounding calculation industrially routine
Transport PDE model ≤ 2 Lumped model, empirical correlation, or validated numerical package industrially routine
Mass and energy balance — authority ≤ 3 · industrially routine
Computes
Constrains flows, inventories, compositions, and heat by conservation.
Example
Reconciling metered flows and inventories around a unit by conservation to catch a measurement error.
Placement
edge
Must beat
Direct inventory and flow reconciliation
Use when
Boundaries, phases, sources, and measurements are defined.
Poor fit when
Unmeasured flows, phase change, or accumulation terms are omitted.
Data burden
Topology, properties, flow/composition/temperature measurements, and boundary conditions.
Authority basis
Conservation of mass and energy is a governing constraint, not a fitted model; Phase 49c places it in the hard-constraint layer. Ceiling matches the register's other deterministic state estimators and still depends on measured flows.
Validation
Closure residuals, units, transients, sensor faults, and independent inventory checks.
Failure modes
Wrong boundary, missing species, property error, and compensating sensor biases.
Independent protection
Protective limits use independently justified measurements and design bases.
Evidence / maturity
engineering judgement / industrially routine
Sources
Phase 49a adversarial evidence findings (internal evidence record; not published); Phase 49c chemical/biological evidence-closure and adversarial findings (internal evidence record; not published)
Arrhenius reaction-kinetics model — authority ≤ 2 · industrially routine
Computes
Relates reaction-rate constants to temperature within a fitted mechanism.
Example
Relating a reaction rate to temperature within a fitted mechanism over its validated parameter range.
Placement
edge
Must beat
Validated empirical rate table or conservative design case
Use when
Mechanism, parameter range, and transport assumptions match the process.
Poor fit when
Mass transfer, catalyst ageing, side reactions, or thermal runaway dominate outside calibration.
Data burden
Rate measurements across temperature, composition, pressure, and relevant catalyst state.
Authority basis
Phase 49c: kinetics is a fitted closure and does not inherit hard-constraint status from the governing model it sits inside; advisory only, within its validated parameter range.
Validation
Independent experiments, parameter uncertainty, extrapolation, heat-release, and sensitivity tests.
Failure modes
Exponential extrapolation, wrong mechanism, transport limitation, and parameter compensation.
Independent protection
Runaway protection is based on independent hazard analysis and protective systems.
Evidence / maturity
mixed / industrially routine
Sources
NIST Chemical Kinetics Database; Phase 49a adversarial evidence findings (internal evidence record; not published); Phase 49c chemical/biological evidence-closure and adversarial findings (internal evidence record; not published)
Equilibrium thermodynamic model — authority ≤ 2 · industrially routine
Computes
Computes phase or reaction equilibrium from thermodynamic relationships.
Example
Computing vapour-liquid equilibrium for a separation where the property method covers the composition range.
Placement
engineering workstation
Must beat
Validated property package, laboratory data, or conservative bounding calculation
Use when
Equilibrium is a valid approximation and the property method covers the composition range.
Poor fit when
Kinetics, metastability, transport, or missing species control behaviour.
Data burden
Species, phases, property parameters, composition, pressure, and temperature range.
Authority basis
Phase 49c closed the NIST source gap for equilibrium data, but the property method (activity model, equation of state) is fitted and treated as soft; advisory only.
Validation
Property comparison, phase-boundary cases, closure, sensitivity, and laboratory checks.
Failure modes
Wrong property method, missing phase, false equilibrium assumption, and extrapolation.
Independent protection
Independent relief, trip, and containment design remains authoritative.
Evidence / maturity
engineering judgement / industrially routine
Sources
Phase 49a adversarial evidence findings (internal evidence record; not published); Phase 49c chemical/biological evidence-closure and adversarial findings (internal evidence record; not published)
Transport PDE model — authority ≤ 2 · industrially routine
Computes
Models spatial diffusion, convection, heat transfer, or species transport.
Example
Modelling species diffusion across a packed bed where spatial gradients drive the design decision.
Placement
engineering workstation
Must beat
Lumped model, empirical correlation, or validated numerical package
Use when
Spatial gradients affect the decision and boundary conditions are defensible.
Poor fit when
Closures or boundaries dominate uncertainty beyond useful resolution.
Data burden
Geometry, material properties, constitutive closures, boundaries, and validation measurements.
Authority basis
Phase 49c: the transport structure is governing, but its constitutive closures and transfer coefficients are fitted and treated as soft; advisory only.
Validation
Grid/time convergence, conservation, benchmark, sensitivity, and transient validation.
Failure modes
Mesh dependence, closure error, wrong boundary, numerical diffusion, and unstable solve.
Independent protection
Safety margins and protection do not rely on a single unverified simulation.
Evidence / maturity
engineering judgement / industrially routine
Sources
Phase 49a adversarial evidence findings (internal evidence record; not published); Phase 49c chemical/biological evidence-closure and adversarial findings (internal evidence record; not published)

Biological

Method Max authority Must beat Maturity
Monod-type growth model ≤ 2 Empirical batch profile or mass-balance trend industrially routine
Fed-batch feed profile ≤ 3 Open-loop recipe with PI/PID trim industrially routine
Raman-plus-PLS bioprocess soft sensor ≤ 1 Offline assay, direct sensor, or simpler spectral calibration piloted
Metabolic flux-balance model ≤ 2 Yield coefficients, mass balance, or empirical pathway analysis piloted
Advanced bioprocess supervisory control ≤ 2 Recipe, cascade PI/PID, ratio, and operator procedure research
Monod-type growth model — authority ≤ 2 · industrially routine
Computes
Relates microbial growth rate to a limiting substrate under fitted assumptions.
Example
Relating microbial growth rate to a limiting substrate for a fermentation matching the fitted assumptions.
Placement
engineering workstation
Must beat
Empirical batch profile or mass-balance trend
Use when
Organism, substrate limitation, inhibition, and operating mode match the fitted model.
Poor fit when
Mixed populations, inhibition, morphology, or unmeasured limitations dominate.
Data burden
Biomass, substrate, product, feed, and environment measurements across batches.
Authority basis
Phase 49c: a fitted growth law is a soft closure regardless of the deterministic form it takes; advisory only, within the fitted organism and operating mode.
Validation
Batch holdout, parameter identifiability, inhibition, contamination, and uncertainty tests.
Failure modes
Wrong limiting factor, population shift, non-identifiability, and batch-to-batch drift.
Independent protection
Containment, sterilisation, and critical limits remain independently protected.
Evidence / maturity
engineering judgement / industrially routine
Sources
Phase 49a adversarial evidence findings (internal evidence record; not published); Phase 49c chemical/biological evidence-closure and adversarial findings (internal evidence record; not published)
Fed-batch feed profile — authority ≤ 3 · industrially routine
Computes
Schedules substrate addition using time, measurements, or a fitted growth model.
Example
Scheduling substrate addition over a fed-batch run from time and measurements against a validated trajectory.
Placement
device
Must beat
Open-loop recipe with PI/PID trim
Use when
The process and assay evidence support a repeatable feed trajectory.
Poor fit when
Culture state is poorly observed or batch variability invalidates the profile.
Data burden
Batch trajectories, feed records, assays, oxygen, pH, and product outcomes.
Authority basis
Phase 49c records open-loop feed profiles with PI/PID trim as the deterministic reality baseline. The ceiling covers that recipe/PID path only — a profile scheduled from a fitted growth model is soft and capped at 2.
Validation
Batch holdout, missed-feed, sensor fault, contamination, saturation, and fallback tests.
Failure modes
Overfeed, oxygen limitation, inhibition, wrong batch phase, and actuator error.
Independent protection
Independent limits protect pressure, temperature, gas, and containment.
Evidence / maturity
engineering judgement / industrially routine
Sources
Phase 49a adversarial evidence findings (internal evidence record; not published); Control Theory Field Guide; Phase 49c chemical/biological evidence-closure and adversarial findings (internal evidence record; not published)
Raman-plus-PLS bioprocess soft sensor — authority ≤ 1 · piloted
Computes
Estimates concentration or quality attributes from calibrated spectra.
Example
Estimating product concentration between assays from calibrated Raman spectra spanning lots and probes.
Placement
edge
Must beat
Offline assay, direct sensor, or simpler spectral calibration
Use when
Reference assays and spectra cover lots, instruments, probes, and process phases.
Poor fit when
Calibration transfer, fluorescence, fouling, or sparse reference assays dominate.
Data burden
Time-aligned spectra and trusted assays across batches, probes, and maintenance states.
Authority basis
Phase 49c: calibration is not transferable across probes, lots, and maintenance states without recalibration in context, so the learned/hybrid ceiling is defaulted to 1. Level 0 for any released-quality decision made alone.
Validation
Batch/lot holdout, calibration transfer, probe-fault, uncertainty, drift, and assay reconciliation.
Failure modes
Spectral drift, fouling, batch confounding, calibration transfer error, and false confidence.
Independent protection
Critical quality and safety decisions retain required independent confirmation.
Evidence / maturity
engineering judgement / piloted
Sources
Phase 49a adversarial evidence findings (internal evidence record; not published); NIST AI Risk Management Framework 1.0 (NIST AI 100-1); Phase 49c chemical/biological evidence-closure and adversarial findings (internal evidence record; not published)
Metabolic flux-balance model — authority ≤ 2 · piloted
Computes
Computes feasible metabolic fluxes under stoichiometric and objective assumptions.
Example
Computing feasible metabolic fluxes under stoichiometric constraints for a credible organism and condition.
Placement
engineering workstation
Must beat
Yield coefficients, mass balance, or empirical pathway analysis
Use when
Network, constraints, and objective are credible for the organism and condition.
Poor fit when
Regulation, kinetics, mixed populations, or objective ambiguity dominate.
Data burden
Stoichiometry, uptake/secretion bounds, biomass objective, and validation assays.
Authority basis
Phase 49c: stoichiometry is governing, but the objective function is an assumption and alternate optima are unconstrained; advisory only.
Validation
Flux consistency, alternative objectives, knockout/perturbation, uncertainty, and assay checks.
Failure modes
Wrong objective, missing pathway, unconstrained alternate optimum, and condition mismatch.
Independent protection
The model cannot set safety-critical feeds or containment limits.
Evidence / maturity
engineering judgement / piloted
Sources
Phase 49a adversarial evidence findings (internal evidence record; not published); Phase 49c chemical/biological evidence-closure and adversarial findings (internal evidence record; not published)
Advanced bioprocess supervisory control — authority ≤ 2 · research
Computes
Coordinates feeds, gases, temperature, or harvest timing from models and soft sensors.
Example
Coordinating feed, gas, and temperature from models and soft sensors where it beats the classical baseline across batches.
Placement
supervisory
Must beat
Recipe, cascade PI/PID, ratio, and operator procedure
Use when
It beats the classical baseline across batches with bounded, reviewable actions.
Poor fit when
Culture state, contamination, assay delay, or batch variability cannot be bounded.
Data burden
Representative batches, interventions, assays, disturbances, and actuator constraints.
Authority basis
Phase 49c: bounded advisory authority only, inside an envelope held by an independent non-learned layer, with zero risk-reduction credit; recorded as a feasibility case, not a class capability.
Validation
Batch holdout, adversarial disturbance, soft-sensor fault, constraint, rollback, and quality tests.
Failure modes
Wrong biological state, delayed assay, model drift, overfeed, and objective conflict.
Independent protection
Basic control, containment, sterilisation, trips, and operator stop remain independent.
Evidence / maturity
engineering judgement / research
Sources
Phase 49a adversarial evidence findings (internal evidence record; not published); NIST AI Risk Management Framework 1.0 (NIST AI 100-1); Phase 49c chemical/biological evidence-closure and adversarial findings (internal evidence record; not published)

Domain limits

Review status

This register is generated from a corpus-owned Draft register and its Phase 49c authority ceilings were author-reviewed in August 2026. It is a decision aid to make the next engineering question explicit — it does not replace hazard analysis, detailed design review, or the applicable safety and cybersecurity lifecycle. Return to the authority gate for the ladder, the pre-flight question, and the envelope architecture every row is scored against.

Trust Boundary — Engineering Judgment Required

This site is an independent educational reference for industrial automation standards. It paraphrases and organizes guidance in original language; it is not a substitute for the official published standards, professional engineering judgment, or legal review, and content has not been independently verified against current published editions.

Items marked Review pending await technical review against the identified edition. Items marked Planned have no reviewed source material behind them. Do not rely on this site for compliance determinations, safety-critical design decisions, or legal interpretation.