Safety. This is a reasoning aid, not a work instruction. Electrical work is performed de-energized and verified by qualified personnel under your site’s LOTO procedures and the device manufacturer’s manual. Measure, don’t guess — every branch below ends at a measurement. Treat the enclosure as energized until proven otherwise.

Overview

An analog loop reports a process value as a current (4–20 mA) or a voltage (0–10 V), and the number it reports already tells you how it is failing. A 4–20 mA loop is a series current circuit with a live zero: 4 mA is 0% and 20 mA is 100%, so a reading below 4 mA is not a legitimate value — it is the loop telling you it is broken or unpowered. That built-in broken-wire detection is the diagnostic gift of live zero, and it is why this page sorts by the reading first.

This page covers 4–20 mA current loops and 0–10 V signals at the fault-domain level: what each symptom class implicates, the discriminating check, and the fix direction. It routes to the 4–20 mA wiring guide and 0–10 V wiring guide for the underlying wiring — it does not re-explain them.

Start Here

Before touching a terminal, observe and record:

Decision Tree

flowchart TD
    R{What does it read?} --> Z[Zero / below 4 mA]
    R --> F[Full-scale / over-range]
    R --> N[Noisy / jumpy]
    R --> O[Offset / wrong but stable]

    Z --> Z1[Broken wire / open terminal\nlive zero: 0 mA is unambiguous]
    Z --> Z2[Dead loop power / blown fuse]
    Z --> Z3[Transmitter fault]
    Z --> Z4[Reversed polarity]

    F --> F1[Short / wetted conductor]
    F --> F2[Wrong input range configured]
    F --> F3[Double-powered passive loop\ntwo active ends — magic smoke]

    N --> N1[Shield grounded both ends → hum]
    N --> N2[VFD / motor-cable coupling]
    N --> N3[Ground loop → needs isolator]

    O --> O1[Scaling / range config mismatch]
    O --> O2[Loop resistance > compliance\nclips near 100%]
    O --> O3[Calibration drift]
    O --> O4[0–10 V long run: voltage-divider error]

    Z1 --> M[Any branch → bisect:\nseries mA + inject a known signal]
    F1 --> M

Likely Causes

Reads zero / below 4 mA — the path is broken or unpowered

Reads full-scale / over-range — too much current or driven past span

Reads noisy / jumpy — coupled interference or a ground problem

Reads offset / wrong-but-stable — config, budget, or calibration

0–10 V-specific — the long-run voltage divider

A voltage signal shares a reference and drops across conductor resistance, so a long run behaves as an unintended voltage divider — the card sees less than the source, reading low and load-dependent. Check: measure voltage at the source versus at the card; a difference is the divider error. Fix direction: shorten the run, increase gauge, or switch to 4–20 mA, which is immune. The mechanism is covered in the 0–10 V wiring guide.

What to Measure

Bisect the loop — split it in half at each step so you know which side owns the fault:

For the wiring context behind these checks, see the 4–20 mA and 0–10 V guides; retain results on the loop sheets. Injection technique above is generally accepted practice — verify for your installation.

Common Root Causes

Symptom Likely cause First check Typical fix
Reads 0 / below 4 mA Broken wire or open terminal Series mA = 0; continuity de-energized Repair the open connection
Reads 0, 2-wire device Dead loop power / blown fuse Loop voltage at transmitter terminals Restore supply, replace fuse
Reads 0, wiring proves good Transmitter fault Inject known mA at the card Replace/service per device manual
Pinned full-scale Short, wetted conductor, or wrong range Insulation resistance; card range vs design Reseal/replace; set range to match
Nonsense / damaged input Double-powered passive loop Active/passive on both manuals One power source per loop
Noisy, hum tracks load Shield grounded both ends Shield landing points Land analog shield one end only
Noise when a drive runs VFD / motor-cable coupling Cable routing vs VFD output Separate runs, cross at 90°
Offset + noise across grounds Ground loop Voltage between ground refs Add a loop isolator
Steady wrong number Scaling / range config mismatch EU scaling vs ranged span Correct the scaling
Reads low, clips near 100% Loop resistance > compliance Loop-resistance budget at 20 mA Heavier gauge / higher supply
0–10 V reads low, load-dependent Long-run voltage divider Voltage at source vs card Shorten run / go 4–20 mA

When It’s Not What It Looks Like

Trust Boundary — Engineering Judgment Required

This site is an independent educational reference for industrial automation standards. It paraphrases and organizes guidance in original language; it is not a substitute for the official published standards, professional engineering judgment, or legal review, and content has not been independently verified against current published editions.