Safety. This is a reasoning aid, not a work instruction. Diagnosis and testing are performed by qualified personnel under your site’s LOTO procedures. VFD DC bus capacitors hold a lethal charge after power removal — observe the drive’s marked discharge wait time before touching any terminal. Insulation testing is done de-energized with the drive output disconnected. Measure, don’t guess.

Overview

A variable frequency drive trips to protect itself and the motor. The vendor’s numeric code tells you which protection operated — it does not tell you the cause, and no two manufacturers number them the same way. Always read the actual code out of the drive against your drive’s own fault-code list; this page never reproduces one. What it does instead is reason about the fault CATEGORIES those codes fall into, so the code becomes a starting branch rather than an answer.

The most useful single question is not “what number?” but “when does it trip?” — on decel, on accel, under steady load, after warm-up, or on enable. The correlation with a phase of operation points at the subsystem far more reliably than the code.

Start Here

Before touching anything, observe and note:

Decision Tree

flowchart TD
    A[Drive faulted?] -->|No fault, shaft still| NORUN[Enable / reference / STO gap]
    A -->|Yes, has a code| B{When does it trip?}
    B -->|On decel / overhauling load| OV[Overvoltage - bus]
    B -->|Instant on run or accel| OC[Overcurrent / output short]
    B -->|After minutes-hours running| OT[Overtemperature]
    B -->|On enable, leakage to earth| GF[Ground fault]
    B -->|On power events / at power-up| UV[Input / undervoltage]
    B -->|Sporadic, only under load| EMC[Nuisance trip - EMC / coupling]

    OV --> OVc[Extend decel ramp;<br/>add brake resistor/regen]
    OC --> OCc[OFFLINE insulation + ring out<br/>motor & cable; check accel/motor data]
    OT --> OTc[Cabinet ambient, airflow,<br/>carrier frequency, derate]
    GF --> GFc[OFFLINE megger motor & cable<br/>to ground - drive disconnected]
    UV --> UVc[Measure 3 input phases;<br/>lost phase / precharge / terminals]
    NORUN --> NRc[Run permissive, reference SOURCE,<br/>direction, STO]
    EMC --> EMCc[Shields 360 both ends, segregation,<br/>PE/filter bonding - not parameters]

Likely Causes

Overvoltage (DC bus)

Overcurrent / output short

Overtemperature

Ground fault

Input / undervoltage

Motor won’t run — but no fault is shown

Nuisance trips under load (EMC / coupling)

What to Measure

Every category resolves to a measurement, not a guess:

Common Root Causes

Symptom Likely cause First check Typical fix
Trips on decel Regen bus overvoltage; decel too fast Extend decel ramp — does it clear? Longer decel or brake resistor/regen
Instant trip on run/accel Output short / motor-cable fault, or accel too aggressive OFFLINE insulation + ring out Repair insulation; soften accel/fix motor data
Trips after warm-up Cooling / ambient / carrier frequency Cabinet ambient + airflow Restore cooling, derate, lower carrier
Trips on enable, leakage to earth Ground fault in motor or cable OFFLINE megger to ground Repair motor/cable insulation
Trips on power events / won’t charge Supply, lost input phase, precharge Measure 3 input phases Correct supply; service precharge/terminals
Ready but shaft still, no fault Enable/reference-source/direction/STO gap Walk the permissive chain Satisfy permissive; select right reference
Sporadic trips only under load EMC coupling, shield/bonding/segregation Scope idle vs loaded Fix shielding/segregation/bonding

When It’s Not What It Looks Like

Trust Boundary — Engineering Judgment Required

This site is an independent educational reference for industrial automation standards. It paraphrases and organizes guidance in original language; it is not a substitute for the official published standards, professional engineering judgment, or legal review, and content has not been independently verified against current published editions.