Troubleshooting: Motor Won't Start
One question splits the whole problem: does the contactor pull in? That boundary separates the control circuit from the power circuit before you measure anything.
Safety. This is a reasoning aid, not a work instruction. Diagnosis and testing are performed by qualified personnel under your site’s LOTO procedures. Rotate a shaft by hand only under confirmed zero-power, zero-stored-energy conditions. Measure across live power terminals only when trained and equipped to do so. Measure, don’t guess.
Overview
A motor fed by a starter — across-the-line contactor, star-delta, or soft starter in bypass — that will not start is one of the most common field calls, and one of the most over-diagnosed. The trap is chasing the motor when the fault is in the control circuit, or chasing the control circuit when a power leg is open.
This page is for starter-driven and general no-starts. If the motor is fed by a variable frequency drive, the failure modes are different — start at Troubleshooting VFD Faults instead.
Start Here
The pivot question does the heavy lifting: does the contactor pull in when you command a start? Before touching anything, observe:
- Does the contactor energize? Listen/look for the pull-in. This alone splits control-side from power-side.
- Any overload trip indicator? A tripped overload explains both a no-pull-in and an open power leg.
- Is control power present? A dead CPT kills the whole control circuit.
- Any sound from the motor? A hum with no rotation is a specific power-side signature (single-phasing).
- What changed? New wiring, a recent trip, a jammed load, a brake that may not be releasing.
Decision Tree
flowchart TD
A[Does the contactor pull in?] -->|No| CTRL[Control circuit]
A -->|Yes, but no rotation| PWR[Power circuit]
A -->|Pulls in, motor hums| HUM[Lost phase / single-phasing]
A -->|Starts, then overload trips| OL[Load / sizing / transition]
CTRL --> C1[E-stop / interlock open]
CTRL --> C2[Overload tripped - aux contact open]
CTRL --> C3[No start command at the coil]
CTRL --> C4[Control power / CPT dead]
CTRL --> C5[Seal-in / holding circuit broken]
PWR --> P1[Blown fuse / lost phase]
PWR --> P2[Overload heater / element open]
PWR --> P3[Motor connection wrong or open]
PWR --> P4[Mechanical seize / brake still set]
HUM --> H1[One open leg: fuse, contact pole,<br/>conductor - measure all 3 phases]
OL --> O1[Load too high / jammed]
OL --> O2[Overload set below FLA]
OL --> O3[Star-delta transition fault]
Likely Causes
Contactor does not pull in — control circuit
- E-stop or interlock open — any series stop, guard interlock, or safety relay contact breaks the string. Check each is satisfied and its contact actually closed, not merely reset at the operator station.
- Overload tripped (aux contact open) — the overload’s auxiliary contact sits in the control string; a trip opens it. Looks like: ran, tripped, won’t restart until reset (and won’t reset until cooled). Check the trip indicator and aux-contact state.
- No start command — the pushbutton, PLC output, or run signal never reaches the coil. Check for the command at the control input, not at the HMI — an HMI “start” that never became a real output is a classic trap.
- Control power absent — a dead CPT, blown control fuse, or lost control supply. Nothing in the control circuit works. Route to control power wiring.
- Seal-in / holding circuit broken — a start that won’t hold: the contactor chatters or drops the instant the button is released, because the seal-in auxiliary contact or its wiring is open. See the seal-in topology in the motor-starter wiring guide.
Contactor pulls in but motor does not turn — power circuit
- Blown fuse / lost phase on one line — one of L1/L2/L3 missing downstream of the contactor. Motor hums, will not accelerate, trips overload. Check voltage on all three phases at the load side.
- Overload heater / element open — an open thermal element or burned heater breaks a power leg. Check continuity/voltage across each overload pole with the contactor closed.
- Motor connection wrong or open — a terminal-box wiring error (wrong star/delta arrangement) or an open winding lead. Check terminals against the nameplate diagram; check winding-resistance balance across phases.
- Mechanical seizure or brake still set — the motor is fine but the load or a failed-closed brake holds the shaft. Full current, overload trip. Try to rotate the shaft by hand under zero-power conditions; confirm the brake releases.
Motor hums / single-phases
- What it looks like — loud hum, no rotation from rest, rapid heating, overload trip in seconds. Will sometimes run if spun by hand — a giveaway.
- Cause — a lost phase: one open fuse, one failed contact pole, one broken conductor or terminal. A three-phase motor cannot start on two phases.
- Check — measure all three phases at the motor terminals with the contactor closed; the missing leg is the fault.
Trips overload on start
- What it looks like — begins to turn, accelerates slowly or partially, then trips; may restart and trip repeatedly.
- Causes — load too high or jammed; overload set below the motor’s actual FLA; excessive start frequency without cooling; or a star-delta transition fault — bad transition timer, open transition contact, or too-early switchover dropping the motor off during acceleration.
- Check — overload setting against nameplate FLA; test the load free/unjammed; on star-delta, verify the transition sequence and timing — wiring in the motor-starter guide.
What to Measure
- Voltage present at each stage — supply L1/L2/L3 at the disconnect, the line side of the contactor, the load side of the contactor, and the motor terminals. Walking the voltage down these stages localizes an open to one segment.
- Control voltage at the coil — is the coil actually seeing pull-in voltage? No coil voltage sends you into the control-circuit branch; coil voltage present with no pull-in means a failed coil or contactor. See control power wiring.
- Overload state — tripped or reset, and the aux-contact state. A tripped overload explains both a no-pull-in (aux open in the control string) and a power-leg open (element open) — check it early.
Common Root Causes
| Symptom | Likely cause | First check | Typical fix |
|---|---|---|---|
| Contactor won’t pull in | E-stop/interlock open in control string | Each interlock satisfied and closed? | Restore the open contact |
| Won’t pull in, ran fine earlier | Overload tripped, aux contact open | Overload trip indicator | Find load cause, reset |
| Won’t pull in, whole control dead | Control power / CPT / fuse | Voltage downstream of CPT | Restore control power |
| Starts but drops out on release | Seal-in / holding circuit broken | Seal-in aux contact and wiring | Repair seal-in path |
| Pulls in, no rotation | Lost phase / blown fuse | Voltage on all 3 phases at load side | Replace fuse / repair open leg |
| Pulls in, motor hums, heats | Single-phasing | Measure 3 phases at motor terminals | Restore the missing leg |
| Pulls in, full current, no turn | Mechanical seize / brake set | Rotate shaft by hand (zero power) | Free the load / release brake |
| Starts then trips overload | Load, undersized OL, or transition fault | OL setting vs FLA; star-delta timing | Correct sizing/load/transition |
When It’s Not What It Looks Like
- A “dead motor” that is a tripped overload. The motor and power circuit are fine; the overload’s aux contact has opened the control string. Reads like a no-start; it’s a control-side symptom of a power-side event — find why it tripped before resetting.
- A “control fault” that is single-phasing. The contactor pulls in perfectly, so the control side looks proven — but a lost phase downstream means no torque. Always confirm all three phases at the motor when the contactor closes but nothing turns.
- A “motor failure” that is a brake that never released. Full current and an overload trip look like a shorted or seized motor; the shaft is simply held by a failed-closed holding brake. Confirm brake release first.
- A “start button fault” that is a broken seal-in. The motor runs only while the button is held. The start command works; the holding contact or its wiring is open — a motor-starter seal-in problem, not a bad pushbutton.
- An overload trip that is really a transition fault. On star-delta, a mistimed or open transition looks like an oversized load tripping the overload — but the motor was accelerating fine until the switchover.
Related Pages
- How to Wire a Motor Starter — seal-in, overload, and star-delta transition wiring
- Control Power Wiring — CPT, control fusing, and the coil circuit
- Troubleshooting VFD Faults — for drive-fed motors instead of starters
- Motor Fundamentals — nameplate, FLA, slip, and torque behaviour
- Motor Troubleshooting Decision Tree — the broader motor/drive routing page
This site is an independent educational reference for industrial automation standards. It paraphrases and organizes guidance in original language; it is not a substitute for the official published standards, professional engineering judgment, or legal review, and content has not been independently verified against current published editions.