Safety. This is a reasoning aid, not a work instruction. Diagnosis and testing are performed by qualified personnel under your site’s LOTO procedures. Rotate a shaft by hand only under confirmed zero-power, zero-stored-energy conditions. Measure across live power terminals only when trained and equipped to do so. Measure, don’t guess.

Overview

A motor fed by a starter — across-the-line contactor, star-delta, or soft starter in bypass — that will not start is one of the most common field calls, and one of the most over-diagnosed. The trap is chasing the motor when the fault is in the control circuit, or chasing the control circuit when a power leg is open.

This page is for starter-driven and general no-starts. If the motor is fed by a variable frequency drive, the failure modes are different — start at Troubleshooting VFD Faults instead.

Start Here

The pivot question does the heavy lifting: does the contactor pull in when you command a start? Before touching anything, observe:

Decision Tree

flowchart TD
    A[Does the contactor pull in?] -->|No| CTRL[Control circuit]
    A -->|Yes, but no rotation| PWR[Power circuit]
    A -->|Pulls in, motor hums| HUM[Lost phase / single-phasing]
    A -->|Starts, then overload trips| OL[Load / sizing / transition]

    CTRL --> C1[E-stop / interlock open]
    CTRL --> C2[Overload tripped - aux contact open]
    CTRL --> C3[No start command at the coil]
    CTRL --> C4[Control power / CPT dead]
    CTRL --> C5[Seal-in / holding circuit broken]

    PWR --> P1[Blown fuse / lost phase]
    PWR --> P2[Overload heater / element open]
    PWR --> P3[Motor connection wrong or open]
    PWR --> P4[Mechanical seize / brake still set]

    HUM --> H1[One open leg: fuse, contact pole,<br/>conductor - measure all 3 phases]

    OL --> O1[Load too high / jammed]
    OL --> O2[Overload set below FLA]
    OL --> O3[Star-delta transition fault]

Likely Causes

Contactor does not pull in — control circuit

Contactor pulls in but motor does not turn — power circuit

Motor hums / single-phases

Trips overload on start

What to Measure

Common Root Causes

Symptom Likely cause First check Typical fix
Contactor won’t pull in E-stop/interlock open in control string Each interlock satisfied and closed? Restore the open contact
Won’t pull in, ran fine earlier Overload tripped, aux contact open Overload trip indicator Find load cause, reset
Won’t pull in, whole control dead Control power / CPT / fuse Voltage downstream of CPT Restore control power
Starts but drops out on release Seal-in / holding circuit broken Seal-in aux contact and wiring Repair seal-in path
Pulls in, no rotation Lost phase / blown fuse Voltage on all 3 phases at load side Replace fuse / repair open leg
Pulls in, motor hums, heats Single-phasing Measure 3 phases at motor terminals Restore the missing leg
Pulls in, full current, no turn Mechanical seize / brake set Rotate shaft by hand (zero power) Free the load / release brake
Starts then trips overload Load, undersized OL, or transition fault OL setting vs FLA; star-delta timing Correct sizing/load/transition

When It’s Not What It Looks Like

Trust Boundary — Engineering Judgment Required

This site is an independent educational reference for industrial automation standards. It paraphrases and organizes guidance in original language; it is not a substitute for the official published standards, professional engineering judgment, or legal review, and content has not been independently verified against current published editions.