PLC Algorithms & Equipment Staging
Queues, ranking, and the logic that decides how many pumps run and which one starts next — the data-structure side of PLC programming.
Scope. This page covers application-level algorithms: FIFO queues and shift registers for tracking, sorting at PLC scale, and the equipment-staging family (lead-lag, demand staging, runtime equalization, sequenced starts, failed-start replacement, load shedding). It does not re-teach state-machine design, function-block design, or language selection — those live on the linked sibling pages. All code fragments are illustrative pseudocode with invented tags, not platform code.
Why data-structure algorithms appear in PLC code
Three plant realities force them in. Order matters — the first product onto the conveyor should be the first one labelled, so something must remember arrival order. History matters — alarms and samples need a bounded memory of recent events. Fairness matters — when three identical pumps share one duty, running the same pump until it wears out while its twins sit idle is poor asset management. Queues answer the first two; ranking and staging answer the third.
FIFO queues
First In, First Out: the earliest value loaded is the first unloaded. Typical uses are product and pallet tracking, machine job queues, batch/recipe request queues, and buffering alarms or barcodes until a downstream system collects them.
A FIFO is an array plus a write index, a read index, and a count — with the indexes wrapping at the end of the array, which turns fixed storage into a circular buffer (illustrative — not platform code):
IF LoadRequest AND (QueueCount < QueueSize) THEN
Queue[WriteIndex] := NewValue;
WriteIndex := WriteIndex + 1;
IF WriteIndex >= QueueSize THEN WriteIndex := 0; END_IF;
QueueCount := QueueCount + 1;
END_IF;
Guard both ends — a full check on load, an empty check on unload — and drive both from one-shot edges, or one product gets queued three scans in a row. Most platforms provide this ready-made; named purely as examples: Rockwell’s paired FFL/FFU instructions, Siemens FIFO library blocks for S7-1200/1500, and Beckhoff ring-buffer function blocks in the TwinCAT libraries. Behaviour differs per platform — consult your platform’s documentation.
When each entry carries more than an ID (recipe, barcode, reject flag, destination), queue a structured record instead of a bare integer — at which point Structured Text is normally the clearer tool.
Conveyor shift registers
When product advances one physical position per encoder pulse or machine cycle, the array index can be the position: every pulse shifts each element one slot along, a new ID enters at position zero, and whatever falls off the end is the product arriving at the exit station. Ladder bit-shift instructions handle single-bit tracking; integer IDs shift with a short copy loop. The shift must be edge-triggered — a maintained trigger smears the whole array in a few scans.
Sorting at PLC scale
PLC arrays are small — three to a few dozen equipment items — so algorithmic
efficiency is largely irrelevant and bubble sort — a short, easy-to-verify
sort — is the honest workhorse. The refinement that matters more than the
algorithm: sort an index array and leave the data alone. Initialize
Rank[] to 0..N-1, then order it by comparing the runtime that each index
points at:
IF Pump[Rank[i]].RuntimeHr > Pump[Rank[i+1]].RuntimeHr THEN
TempIndex := Rank[i]; Rank[i] := Rank[i+1]; Rank[i+1] := TempIndex;
END_IF;
Rank[0] is now the first-choice pump, while every pump record stays at its
original HMI- and alarm-mapped address.
The equipment-staging family
The scenario: several similar units — pumps, compressors, chillers, fans, boilers — share one duty, and the program decides how many run and which ones. Every variant chases the same goals: meet demand, balance wear, skip unavailable units, respect minimum run/stop times, stagger starts, and rotate the lead role.
flowchart TD
A[Demand calculation] --> B[Required unit count / capacity]
B --> C[Availability filtering]
C --> D[Ranking — runtime / score / priority]
D --> E[Start-stop selection]
E --> F[Sequenced commands<br/>staggered, feedback-verified]
F --> G[Alarm & fallback handling]
G -.failed start.-> D
Lead-lag selection by runtime
Among units that are available, unfaulted, and past their minimum off-time, select the lowest accumulated runtime as the next lead. A selection loop in Structured Text finds the index; Ladder rungs gated on that index issue the actual start commands and permissives. If no unit qualifies, that is an alarm — not a silent no-op. This is the pattern behind duty rotation on lead-lag pump sets — see intake and raw water pumping for it applied in a water utility.
Demand-based staging — with anti-hunting
How many units run follows demand (level, pressure, flow, or a PID output). A constructed teaching example for three pumps — thresholds and times are examples, not requirements:
| Condition | Action |
|---|---|
| demand above 70 % for 30 s | stage up to 2 pumps |
| demand above 90 % for 30 s | stage up to 3 pumps |
| demand below 75 % for 60 s | stage down to 2 pumps |
| demand below 45 % for 60 s | stage down to 1 pump |
Two protections prevent hunting: a dead-band (the stage-down threshold sits well below the stage-up threshold, so normal demand ripple cannot cycle a pump), and delays (an on-delay before staging up, a typically longer off-delay before staging down). Per-unit minimum run and stop times are the third layer, protecting the equipment itself.
Runtime accumulation and equalization
Accumulate runtime while confirmed running feedback is true — never from the start command, which counts hours a failed motor never ran. Make the accumulator retentive, guard overflow, allow authorized correction after maintenance, and keep lifetime hours, since-maintenance hours, and a start counter as separate tags.
Equalization then works both edges: start the lowest-runtime available unit; stop the highest-runtime running unit. Where starts age the machine more than hours (compressors especially), rank by a weighted score of runtime and start count instead — the weights are engineering judgment per equipment type.
The selection strategies, compared
| Strategy | Rule | Trade-off |
|---|---|---|
| Runtime lead-lag | Lowest hours starts next | Balances wear; needs trustworthy runtime data |
| Round-robin | Advance the lead index each cycle | Simple; wear balance only approximate |
| First-available | First qualifying unit from index 0 | Trivial; unit 1 wears far faster |
| Fixed lead-lag | Permanent lead/lag/standby roles | Predictable; no automatic balancing |
| Priority-based | Priority group first, runtime within it | Keeps standby/rental units in reserve |
| Capacity-based | Evaluate unit combinations vs required capacity | Handles mixed sizes; optimization-grade logic, normally ST or supervisory |
Sequencing, failure, and shedding
The staging state machine. A robust controller does not switch outputs straight from demand comparisons — it sequences: select → command start → wait for running feedback → confirm stage, with a fault path from every waiting state. That is what stops three pumps being commanded in one scan. State-machine design itself is covered on the state machines page; staging is a disciplined application of it.
Start-delay sequencing. Large motors starting together stack inrush. Stagger the starts, keying each delay from the previous unit’s confirmed feedback — so a failed start pauses the sequence instead of piling the next unit onto a fault.
Failed-to-start replacement. No running feedback within the timeout: latch a failed-to-start alarm, mark the unit unavailable, re-run the selection, and promote the next-ranked unit. Do not retry the same failed unit in a loop without a deliberate retry policy.
Load-shedding queue. The same machinery in reverse for electrical demand: shed the lowest-priority load group when demand exceeds a limit, wait and re-evaluate, shed the next group only if still needed — and restore in reverse order with delays, so the returning load does not re-trip the limit.
Alarm queue. A circular buffer of alarm records in the PLC is legitimate as a buffer — catching bursts until SCADA collects them. It is a poor database: history, sorting, and filtering belong in the SCADA/HMI/historian layer.
Ladder or Structured Text — and one function block
For this algorithm family the split is unusually clean: Ladder for the event edges and physical layer (one-shots, permissives, staging timers, failed-start rungs, output commands — what maintenance troubleshoots live); Structured Text for everything with a loop in it (sorting, ranking, weighted scores, buffer index math, capacity combinations). The general language-choice question is on the languages overview page.
Structurally, put the whole staging brain in one reusable function block — inputs for demand and per-unit status arrays, outputs for start/stop requests and the selected lead, the filter-rank-select-sequence pipeline inside. One block means one place to test the rules and one instance per pump station. Function-block and POU design is covered under program structure.
Related Pages
- State machines — the staging sequencer is an application of this pattern
- Program structure — POUs and function-block design for the staging block
- Languages overview — the general Ladder/ST/FBD choice
- Intake and raw water pumping — lead-lag pump sets and rotation in a water utility
- Interlocks, permissives & safety trips — the protective layers staging logic sits under
- Safety application patterns — staging never implements the safety function
This site is an independent educational reference for industrial automation standards. It paraphrases and organizes guidance in original language; it is not a substitute for the official published standards, professional engineering judgment, or legal review, and content has not been independently verified against current published editions.