Edition covered
IEC 61131-3 (Ladder Diagram) — IEC 61131-3:2013 (3rd ed.) — verify against your platform's conformance
Content status
Reviewed
Coverage
LD element set and core design patterns (seal-in, I/O mapping, command/feedback, scan order, one-shots, alarm conditioning) at concept level; instruction mnemonics and timer/counter semantics are vendor-specific and deferred to platform docs.
Last reviewed
August 2026
Primary reference
The official published standard — required for final decisions

Confirm the governing edition, jurisdiction, and project-specific requirements before applying anything on this page.

Scope. The Ladder Diagram element set and the design patterns built from it. Language choice lives on the languages overview, tasks/routines/naming on program structure, sequence design on state machines. Ladder sketches are illustrative ASCII with invented tags, not platform code.

Rungs, rails, and evaluation

A ladder routine is a stack of rungs between two power rails: conditions on the left, outputs on the right, each rung one Boolean statement. The visual metaphor is relay-circuit “current flow,” but the semantics are a sequential program — rungs evaluate top to bottom, conditions left to right, once per scan (read inputs → execute logic → write outputs → repeat). That sequential truth drives the scan-order and duplicate-coil behavior further down.

Contacts in series are AND; parallel branches are OR; they nest, so A in series with a B/C branch reads A AND (B OR C) — the seal-in circuit below is the classic combined shape.

The element set, briefly

The start/stop seal-in circuit

The signature ladder pattern — memory without a latch instruction:

|----[/ Stop_PB ]----[/ Overload ]----+----[ Start_PB ]---+----( Motor_Run )----|
|                                     |                   |
|                                     +----[ Motor_Run ]--+

Motor_Run = NOT Stop_PB AND NOT Overload AND (Start_PB OR Motor_Run)

Pressing start makes the rung true and Motor_Run sets; on the next scan the parallel Motor_Run contact — the seal-in or holding contact — keeps the rung true after the button is released. A stop or overload breaks the series chain, the output and its seal branch drop, and the rung stays false until a fresh start press. Two properties make this the preferred run-command shape: every condition that can break it is visible on the same rung, and after a power cycle the coil is false — the motor does not restart itself.

Physical input vs logical meaning — the NC-wired stop

Stop buttons and most protective contacts are wired normally closed: the healthy circuit holds the input TRUE; a pressed button — or a broken wire — drives it FALSE. The ladder therefore examines the stop input with a normally open instruction as a run condition. That looks backwards until you see the point: the wiring fails toward safe — a lost terminal or dead sensor supply is indistinguishable from a pressed stop, and the machine stops. Wired NO instead, a broken stop wire silently disables the stop while the machine keeps running. Keep the physical contact type, electrical state, tag value, instruction type, and process meaning mentally separate — they do not have to match — and name tags for meaning (Stop_OK, EStop_Healthy) so the NO instruction reads correctly. Safety functions proper have requirements beyond this convention — see the final section.

Map I/O once, at the edges

Raw hardware addresses belong in exactly two places: an input map at the top of the program and an output map at the bottom. The logic between works only on descriptive tags.

Input map:   |----[ Local:1:I.Data.0 ]------( Start_PB )----|
Logic:       |----[ Start_PB ]----[ Stop_OK ]----[/ Motor_Fault ]----( Motor_RunCmd )----|
Output map:  |----[ Motor_RunCmd ]----------( Local:2:O.Data.0 )----|

A rewired point becomes a one-line edit, simulation becomes possible, input conditioning (the NC inversion above, debounce, validity checks) has a defined home, and troubleshooting splits into “does the field signal reach the tag?” versus “does the logic use it correctly?”. This pairs with the numbered-routine convention — input map first, permissives/interlocks, sequence, device control, output map last — described on program structure: the numbering makes routine order, and therefore data-flow order, deliberate.

A complete simple motor control (constructed teaching example)

Three tags that are not interchangeable: Motor_RunCmd records that the PLC asked; Motor_RunningFB records that the starter reports running; a current signal can confirm independently. Logic treating the command bit as proof of running cannot detect a tripped starter or a failed start — and will sequence downstream equipment onto a stopped machine. Hence the layered shape most device control is a variation of: permissives → request → command → feedback verification, one purpose per rung, the command written in exactly one place. (Permissive/interlock/trip are defined on the interlocks page; this is just the ladder shape.)

Permissives:   |----[ Stop_OK ]----[ EStop_Healthy ]----[ Overload_OK ]----( Motor_Perm )----|

Start request: |----+--[ Manual_Mode ]--[ Start_PB ]------------+----( Motor_Req )----|
               |    |                                           |
               |    +--[ Auto_Mode ]----[ Seq_Start_Request ]---+

Run command:   |----[ Motor_Req ]----[ Motor_Perm ]----( Motor_RunCmd )----|

Failed start:  |----[ Motor_RunCmd ]----[/ Motor_RunningFB ]----[TON StartFail_Tmr  PRE 5s]----|
               |----[ StartFail_Tmr.DN ]-----------------( Motor_FailedToStart )---------------|

The timer tolerates normal contactor pull-in time; its done bit means the command went unanswered too long — typically dropping the request and requiring an operator reset.

Scan order, and one writer per coil

Rung order matters. A rung that writes Run_Request above the rung reading it gives same-scan response; reversed, the reader reacts one scan late — often harmless, until the delayed bit is a one-shot edge or cross-ordered rungs stack multi-scan delays. The defense is direction: order logic so data flows downhill, producers before consumers.

flowchart LR
    A[Input mapping] --> B[Permissives / interlocks] --> C[Sequence] --> D[Device commands] --> E[Output mapping]

One coil, one writer. A coil writes its bit every scan — true or false — so the same coil on two rungs means the later rung silently decides (“last write wins”): Auto_Start true on one rung, Manual_Start false on a later one, and the motor stays off while monitoring shows a true rung feeding a false coil. This is a defect, not a style choice: merge the conditions into parallel branches on a request tag and keep one primary write per command output. (Latch/unlatch pairs intentionally split one bit across two rungs — the rule targets unintended duplicates.)

One-shots, and values that survive a power cycle

A one-shot is true for a single scan on a false→true transition — it turns a level into an event. A part sensor held 500 ms against a 10 ms scan is true for ~50 scans; a level-driven counter counts 50. One-shots are required wherever something must happen once per occurrence — counting, toggle buttons, pulse commands, log triggers, state transitions; the missing-one-shot symptom is typically “it happened N times instead of once.”

Retentive values survive a power cycle; non-retentive values reinitialize — which behavior a tag or timer has is platform configuration, so check rather than assume. Retention suits totals, runtime hours, recipes, and calibration; it is dangerous for commands and sequence state, which can wake the machine “mid-cycle” in a world that no longer matches. A first-scan routine should validate retained data and force commands and state to a safe default.

Alarm conditioning and analog scaling

A bare comparison makes a chattering alarm. Condition it twice: an on-delay so the condition must persist before asserting, and hysteresis — assert above one value, clear below a lower one (in at 80 °C, out at 77 °C) — so a signal hovering at the threshold cannot cycle it. A complete alarm adds acknowledgment as a deliberate operator action, distinct from the condition clearing.

Analog inputs arrive as raw counts and are converted by linear interpolation — EU = (Raw − RawMin) × span ÷ rawSpan + EUMin — in the input-mapping section, so the rest of the program only sees engineering units; in ladder that is a compute rung or a vendor scaling instruction (the same algorithm appears as Structured Text on the languages overview). Raw endpoints come from the module configuration, not guesswork — and the map should also qualify the signal (under/over-range, which on a 4–20 mA loop can indicate an open circuit; channel faults) so nothing controls from a broken sensor.

Common ladder design mistakes

  1. HMI-only interlocking — the action still fires from another screen or a comms write. Root cause: rule enforced in the presentation layer, not the PLC.
  2. One coil written from multiple rungs — a visibly true rung whose output stays off. Root cause: last-write-wins coil semantics.
  3. Command treated as feedback — sequences advance onto equipment that did not start. Root cause: no independent running signal, or one ignored.
  4. Counting without a one-shot — counts inflated by orders of magnitude. Root cause: level-driven counters increment every scan, not per event.
  5. Latches without a dependable reset — a state no operator action can leave, or a command reappearing at power-up. Root cause: set/reset split across the program; retention not considered.
  6. First-scan behavior ignored — spurious alarms or unexpected commands at power-up. Root cause: retained data and state assumed to self-initialize.
  7. Monolithic rungs — hours to trace one fault. Root cause: no one-rung-one-purpose discipline, no named intermediate tags.
  8. Raw addresses scattered through the logic — a module swap becomes a program-wide edit. Root cause: no mapping layer at the edges.
  9. Undefined abnormal behavior — nobody can say what happens on comms loss, sensor failure, or restart until it happens. Root cause: only the sunny-day path was designed.

Where ladder logic stops: safety functions

Standard ladder in a standard PLC is not adequate protection for hazardous machinery on its own. Emergency stops, guard monitoring, and light curtains normally require safety-rated hardware and architecture — safety controller or relay, dual channels with discrepancy monitoring, monitored manual reset — designed to the applicable PL or SIL. The standard program may read safety status for sequencing and display; it does not implement or bypass the safety function. See safety application patterns and safety circuit wiring.

Trust Boundary — Engineering Judgment Required

This site is an independent educational reference for industrial automation standards. It paraphrases and organizes guidance in original language; it is not a substitute for the official published standards, professional engineering judgment, or legal review, and content has not been independently verified against current published editions.