Why explicit state machines beat ad-hoc logic

A machine sequence is a state machine whether or not the programmer admits it. The only real choice is whether the state is explicit — one variable that names the current step — or implicit, scattered across dozens of coils, seals, and timers that together imply where the machine is.

Ad-hoc sequence logic — “start the pump when these six bits are true, unless this timer, but not if that latch” — has no single source of truth. Two rungs can silently disagree about where the machine is, and the failure mode is the machine that stops “somewhere” that nobody can name, because there is no step to name. Making the state explicit fixes three things that matter on a running plant:

This is the practical, PLC-side companion to the machine state model fundamentals page, which covers the state-model theory (FSM, hierarchical, PackML). This page is about writing it in a controller.

The step, transition, action model

An explicit state machine has three parts:

stateDiagram-v2
    [*] --> Idle
    Idle --> Homing: start & permissives
    Homing --> Ready: homed
    Ready --> Running: cycle start
    Running --> Stopping: stop req / cycle done
    Stopping --> Idle: stopped
    Idle --> Fault: fault
    Homing --> Fault: fault
    Ready --> Fault: fault
    Running --> Fault: fault
    Stopping --> Fault: fault
    Fault --> Idle: cause cleared & reset

The fault transition can fire from any state — that is the point of drawing it as its own path rather than folding it into each step.

Three ways to implement it

IEC 61131-3 does not mandate a state-machine construct; it gives you languages, and the pattern maps onto three of them. Which you use is a house-standard and platform question — consult your platform’s documentation.

SFC — the native language

Sequential Function Chart is the IEC 61131-3 language built for sequences. Steps and transitions are first-class graphical elements: each step carries its actions, each transition carries its guard, and the chart itself doubles as documentation. SFC is the most direct expression of the model when the sequence is genuinely linear or has clean branches. Availability, action qualifiers, and execution semantics are vendor-specific — Rockwell, Siemens (GRAPH), CODESYS, and Beckhoff each diverge from the base standard, so verify against your toolchain.

A CASE on a state variable — the portable pattern

The common, portable approach is a single enumerated State variable switched in a CASE in Structured Text. Each branch holds that state’s actions and evaluates its transition guards, writing the next state. It ports cleanly across platforms and reviews well because the whole machine reads top to bottom. Illustrative only — not platform code:

CASE State OF
  IDLE:     IF StartCmd AND Permissives THEN State := HOMING; END_IF;
  HOMING:   Home();  IF HomeDone THEN State := READY; END_IF;
  READY:    IF CycleStart THEN State := RUNNING; END_IF;
  RUNNING:  RunCycle();  IF CycleDone OR StopReq THEN State := STOPPING; END_IF;
  STOPPING: IF Stopped THEN State := IDLE; END_IF;
  FAULT:    IF ResetPulse AND FaultCleared THEN State := IDLE; END_IF;
END_CASE;

Step-latching in Ladder

Where LD is the house language, each step is a latched bit. The transition rung seals in the next step’s bit and unlatches the current one, so exactly one step bit is on at a time (a “one-hot” chain). It is readable to a maintenance electrician, which is often why it is chosen — but it takes discipline to keep it genuinely one-hot, since nothing in the language enforces the mutual exclusion that a CASE gives for free.

Entry and exit actions, and why one-shots matter

Entry actions run once as a state is entered — start a dwell timer, command a setpoint, reset a counter. Exit actions run once as it is left — stop the motor, clear a request. The word that matters is once.

An action tied to a transition must be one-shot: edge-triggered on the state change, not re-executed every scan the state happens to be active. Re-issuing a “start” command every scan is a classic bug — the command fights itself, or a downstream one-shot never sees a fresh edge and never fires. Detect the transition, act on the edge, move on.

Interlocks and permissives layered over the machine

Interlocks and permissives belong on top of the state machine, not buried inside individual transitions. A permissive is a condition that must be true to allow the machine to proceed; an interlock forces a safe state regardless of where the sequence thinks it is. Keeping them in a separate, clearly labelled layer keeps the sequence readable and the protective logic auditable — the difference between the three protective layers is covered in interlocks, permissives & safety trips.

One boundary is firm: a machine-actuated safety function is not sequence logic and does not live in the state machine at all. It lives in the wired safety circuit and, where a safety controller is involved, in a separate safety application — see safety application patterns. The standard state machine may read safety status, but it never implements the safety function.

Fault states and recovery

A fault is a transition that can fire into a single FAULT state from many states at once. FAULT commands the safe outputs — stop motion, drop non-safety outputs to their de-energized state — and holds. It does not guess and it does not continue.

Recovery is deliberate, never automatic:

  1. The operator (or maintenance) clears the physical cause.
  2. A reset — a monitored edge, never a maintained bit or a permanently held button — acknowledges the fault.
  3. The machine returns to IDLE and usually re-homes, because after a fault the physical position of axes, indexers, and product is unknown and cannot be trusted.

Never let a fault silently self-clear straight back into the running sequence. The one-way trip through FAULT, and the required reset, are what make the machine safe to restart.

Trust Boundary — Engineering Judgment Required

This site is an independent educational reference for industrial automation standards. It paraphrases and organizes guidance in original language; it is not a substitute for the official published standards, professional engineering judgment, or legal review, and content has not been independently verified against current published editions.